Modbus/TCP

Operating Manual PNOZmulti communication interfaces
1001154-EN-13

98

Control Register
A watchdog can be activated in Control Register 255.
If no input bits are set by a Modbus/TCP subscriber within the preset time, the PNOZmulti
will set the input bits to "0".
The table below describes the Modbus/TCP data areas for the watchdog.
A relevant area for the watchdog is defined in each Modbus/TCP data area (Coils (0x), Dis-
crete Inputs (1x), Input Register (3x), Holding Register (4x)). Read/write access will depend
on the Modbus/TCP data area.

Register
(3x, 4x)

Coil/
Descrete Input
(0x, 1x)

Content

High Byte

Low Byte

255

4095...4080

Control Register

See table below

High Byte WD-Trig-

ger

Error Mes-

sage

Reserved Reserved Reserved W-Timer

Bit 2

W-Timer
Bit 1

W-Timer
Bit 0

Low Byte Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved

Bit 15 "Watchdog Trigger": The watchdog can be triggered by setting Bit 15 constantly to
"1", or by a Client writing in the input area of the 128 inputs. The state of the bit when read-
ing is undefined. A 1 or a 0 can be read.
Bit 14 "Error Message": If this bit is set, an error stack entry is generated when the watch-
dog is triggered.
Bits 10 … 8 "WD Timer": If the set time for the watchdog is set, then Bit 15 must be set, or
become set, at the same time.

Watchdog Timer Bit 2

Watchdog Timer Bit 1

Watchdog Timer Bit 0

Watchdog Time

0

0

0

Timer deactivated

0

0

1

100 ms

0

1

0

200 ms

0

1

1

500 ms

1

0

0

1 s

1

0

1

3 s

1

1

0

5 s

1

1

1

10 s

Information
To check whether the watchdog has been triggered, set a virtual input per-
manently to "1".
If the corresponding input in the PNOZmulti is "0", then the watchdog has
been triggered.