1 input data (to the pnozmulti) – Pilz PNOZ mm0p 24VDC User Manual

Page 88

background image

RS232/Ethernet interfaces

Operating Manual PNOZmulti communication interfaces
1001154-EN-13

88

Send input and output data (cf. fieldbus communication)

Request 0x53
The communications partner uses this request to send input data to the PNOZmulti and re-
quest output data from the PNOZmulti (see section entitled "Fieldbus modules", under "Ba-
sics").
As with fieldbus communication, 20 Bytes each are reserved for input and output data (Byte
8 – 27); they are updated approx. every 15 ms.

Byte

Request

Byte

Response

0

0x05

0

0x05

1

0x15

1

0x15

2

0x00

2

0x00

3

0x19

3

0x19

4

0x53

4

0xD3

5

Control Byte

5

Control Byte

6

Reserved

6

Reserved

7

0x00

7

0x00

8

Input Byte 0

8

Output Byte 0

9

Input Byte 1

9

Output Byte 1

10

Input Byte 2

10

Output Byte 2

...

...

...

...

27

Input Byte 19

27

Output Byte 19

28

BCC

28

BCC

29

0x10

29

0x10

Input data (to the PNOZmulti)

Input Byte

Content

0

i7 to i0

1

i15 to i8

2

i23 to i16

3

Reserved

4

Table No.

5

Segment No.

6

Byte 0 of Table x, Segment y

7

Byte 1 of Table x, Segment y

8

.

9

.

10

.

11

.

12

.

5.7.5

5.7.5.1