Byte

Content

Example/Comment

443

O8 ... O15 7th expansion module,

right

0

0

0

0

O3

O2

O1

O0

444

O8 ... O15 8th expansion module,

right

Byte 437 ... Byte 444:
PNOZ mc1p
Byte 421 ... 428:
A7

A6

A5

A4

A3

A2

A1

A0

Byte 437 ... Byte 444:
A15

A14

A13

A12

A11

A10

A9

A8

If an output has a high signal, the corresponding Bit will

contain "1"; if the output is open (low signal), the Bit will

contain "0".
INFORMATION:
On the base units PNOZmulti Mini, the status of the config-

urable inputs/outputs is only displayed if they are config-

ured as outputs in the PNOZmulti Configurator.
Assignment of Bytes on the

base units PNOZmulti Mini:

Byte 416:
0

0

0

0

IM3

IM2

IM1

IM0

Byte 418:
T3
M23

T2
M22

T1
M21

T0
M20

IM19 IM18 IM17 IM16

445 ...

447

Reserved

448

RUN

Depending on the LED status, the following Hex code will

be in Byte 448 ... 460:
00 hex: LED off
FF hex: LED on
30 hex: LED flashes

449

DIAG

450

FAULT

451

IFAULT

452

OFAULT

453

FAULT 1st expansion module, right

454

FAULT 2nd expansion module, right

455

FAULT 3rd expansion module, right

456

FAULT 4th expansion module, right

457

FAULT 5th expansion module, right

458

FAULT 6th expansion module, right

459

FAULT 7th expansion module, right

460

FAULT 8th expansion module, right