2 default settings, 3 description of idns, S-0-1507.0.20 in the chapter entitled – Pilz PNOZ mm0p 24VDC User Manual
Page 73: Description of idns, 1507.0.20 in the chapter entitled

Fieldbus modules
Operating Manual PNOZmulti communication interfaces
1001154-EN-13
73
Default settings
}
IP address: 192.168.1.64
}
Subnet mask: 255.255.255.0
}
Gateway address: 0.0.0.0
}
Device name: PR100011
}
Sercos address: 64
Description of IDNs
}
S-0-0128 CP4 Transition Check
If there is no communication between the PNOZ mc10p and base unit, IDN S-0-0128
will register an error after 30 seconds. It will not be possible to switch to communication
phase 4 (CP4).
}
S-0-1502.0.5 Digital Output PDOUT
Contains the first 4 Bytes of input data. Is always configured in a consumer connection.
}
S-0-1503.0.9 Digital Input PDIN
Contains the first 4 Bytes of output data. Is always configured in a producer connection.
}
S-0-1503.0.19 Digital Input Parameter Channel Receive
Contains 6 Bytes of diagnostic data. Cannot be configured in connections.
}
S-0-1507.0.5 Complex PDOUT
Contains 16 Bytes of table data. Is always configured in a consumer connection with
S-0-1507.0.2.
}
S-0-1507.0.9 Complex PDIN
Contains 16 Bytes of table data. Is always configured in a producer connection with
S-0-1507.0.2.
}
S-0-1507.0.2 Configuration of Function Group Complex Protocol
Configures whether table data is included in both connections. To insert the table data
in both connections, write in CP2 0x0018 before the master reads the connection length
via S-0-1550.0.5 (default confguration). To remove the table data from both connec-
tions, write in CP2 0x001B. Every other value is ignored, but appears in the service
channel (SVC) with error 0x7008.
}
S-0-1507.0.19 Complex Parameter Channel Receive for Object Buffer
Reads 4 Bytes from the object buffer (second step of read access). The address must
be set in advance with S-0-1507.0.20 (see chapter entitled
}
S-0-1507.0.20 Complex Parameter Channel Transmit for Object Buffer
Writes 2 Bytes (first step of object read access) or 3 Bytes (full object write access). If 2
Bytes are written, the address of the object buffer for subsequent read access is set
with S-0-1507.0.19. If 3 Bytes are written, the third byte contains the value that is writ-
ten in the addressed byte of the object buffer (see chapter entitled
).
4.5.7.2
4.5.7.3
- PNOZ mm0.1p PNOZ mm0.2p PNOZ mml1p PNOZ mml2p PNOZ mmc1p ETH PNOZ mmc2p seriell PNOZ mmc3p DP PNOZ mmc6p CAN PNOZ mmc4p DN PNOZ m1p base unit PNOZ m1p base unit coated version PNOZ m0p base unit not expandable PNOZ m2p base module press function PNOZ m3p base unit burner function PNOZ m1p ETH PNOZ m3p ETH PNOZ m0p ETH PNOZ m2p ETH PNOZ m1p ETH coated version PNOZ mi1p 8 input PNOZ mi1p 8 input coated version PNOZ mo1p 4 so PNOZ mo1p 4so coated version PNOZ mo3p 2so PNOZ mo2p 2n/o PNOZ mo2p 2n/o coated version PNOZ mo5p 4 n/o burner PNOZ mo4p 4n/o PNOZ mo4p 4n/o coated version PNOZ ml1p safe link 24VDC PNOZ ml2p safe link PDP PNOZ ms1p standstill / speed monitor PNOZ ms2p PNOZ ma1p 2 Analog Input PNOZ ms3p standstill / speed monitor PNOZms2p HTL PNOZ ma1p coated version PNOZ ml1p coated version PNOZ ms2p TTL coated version PNOZ ms3p HTL PNOZ ms2p TTL PNOZ ms3p TTL PNOZ mi2p 8 standard input PNOZ mc1p PNOZ mc1p coated version PNOZ mc0p Powersupply PNOZ mc5p Interbus PNOZ mc7p CC-Link coated version PNOZ mc7p CC-Link PNOZ mc6p CANopen coated version PNOZmc5.1p Interbus LWL / Fiberoptic PNOZ mc4p DeviceNet coated version PNOZ mc8p Ethernet IP / Modbus TCP PNOZ mc9p Profinet IO PNOZ mc3p Profibus 2 PNOZ mc8p coated version PNOZ mc6p CANopen 2 PNOZ mc4p DeviceNet 2 PNOZ mc2.1p EtherCAT 2 PNOZ mc10p SERCOS III PNOZ mc7p CC-Link 2 PNOZ mc6.1p CANopen 3