beautypg.com

Pilz PNOZ mm0p 24VDC User Manual

Page 47

background image

Fieldbus modules

Operating Manual PNOZmulti communication interfaces
1001154-EN-13

47

61

O8 ... O15 8th expansion

module, right

Sub-Index 54 ... 61:
PNOZ mc1p
Sub-Index 38 ... 45:
A7

A6

A5

A4

A3

A2

A1

A0

Sub-Index 54 ... 61:
A15

A14

A13

A12

A11

A10

A9

A8

If an output has a high signal, the corresponding Bit will contain

"1"; if the output is open (low signal), the Bit will contain "0".
INFORMATION:
On the base units PNOZmulti Mini, the status of the configurable

inputs/outputs is only displayed if they are configured as outputs

in the PNOZmulti Configurator.
Assignment of Bytes on the

base units PNOZmulti Mini:

Sub-Index 33:
0

0

0

0

IM3

IM2

IM1

IM0

Sub-Index 35:
T3M23 T2M22 T1M21 T0;20 IM19

IM18

IM17

IM16

62 ... 64

Reserved

65

RUN

Depending on the LED status, the following Hex code will be in

Sub-Index 65 ... 77:
00 hex: LED off
FF hex: LED on
30 hex: LED flashes

66

DIAG

67

FAULT

68

IFAULT

69

OFAULT

70

FAULT 1: Expansion mod-

ule, right

71

FAULT 2: Expansion mod-

ule, right

72

FAULT 3: Expansion mod-

ule, right

73

FAULT 4: Expansion mod-

ule, right

74

FAULT 5: Expansion mod-

ule, right

75

FAULT 6: Expansion mod-

ule, right

76

FAULT 7: Expansion mod-

ule, right

77

FAULT 8: Expansion mod-

ule, right