Fieldbus modules

Operating Manual PNOZmulti communication interfaces
1001154-EN-13

19

Exception: Table 9 segment 1:
With this table you can set the expanded inputs 24 - 127 and upload the expanded outputs
24 - 127. In contrast to the other tables, in this case the Master not only requests data but
also sends input data to the PNOZmulti via the fieldbus module. Each input is assigned a
Bit in the segment Bytes 0 ... 12 of the input data, each output is assigned a Bit in the seg-
ment Bytes 0 ... 12 of the output data.

ATTENTION!
The expanded input Bits are only updated when table 9 segment 1 is ac-
cessed. In the event of a fieldbus error, input bits i24 ... i127 in the PNOZ-
multi are frozen!

4
5

6

18

Table Number 9

Segment Number 1

Segment Byte 0 (i24 ... i31)

Segment Byte 12 (i120 ... i127)

.
.

.

.
.

.

4
5

6

18

.
.

.

.
.

.

Master

Fieldbus module

Byte

Byte

Segment Byte 0 (o24 ... o31)

Segment Byte 12 (o120 ... o127)

Table Number 9

Segment Number 1