beautypg.com

1 control byte (byte 40) – Pilz PNOZ mm0p 24VDC User Manual

Page 85

background image

RS232/Ethernet interfaces

Operating Manual PNOZmulti communication interfaces
1001154-EN-13

85

Information
If a fieldbus module is configured, virtual inputs cannot be activated via the
integrated interface. In this case the request will be rejected by the PNOZ-
multi with error message 0x63 (request cannot be executed).

Control Byte (Byte 40)
Bits 0 … 2 of the Control Byte contain a watchdog function.
If no virtual inputs are sent by a communications partner within the defined watchdog time
(watchdog timeout), the PNOZmulti sets the virtual inputs to "0".
Control Byte 40:

Reserved Delayed

Response

Error

Message

Reserved Reserved W-Timer

Bit2

W-Timer
Bit1

W-Timer

Bit0

}

Bit 0 - 2: Watchdog Timeout

Watchdog Timer
Bit 2

Watchdog Timer
Bit 1

Watchdog Timer
Bit 0

Watchdog Timeout

0

0

0

Timer deactivated

0

0

1

100 ms

0

1

0

200 ms

0

1

1

500 ms

1

0

0

1 s

1

0

1

3 s

1

1

0

5 s

1

1

1

10 s

}

Bit 3 and 4: Reserved

}

Bit 5 Error Message: Error message

If the bit is set to "1", an error stack entry is generated when the watchdog is triggered.

}

Bit 6 Delayed Response: Delayed response

If the bit is set to "1", the response (send virtual outputs) is sent after a delay of one cy-
cle.

}

Bit 7: Reserved

Information
The watchdog functions of the requests 0x14 segment 0x02 and 0x53 use
the same watchdog timer. In other words, the watchdog timer is reset if ei-
ther request is called.