Fieldbus modules

Operating Manual PNOZmulti communication interfaces
1001154-EN-13

22

The manufacturer-specific part of the object directory is structured as follows:

PDO

Size

Name

Index

Sub-In-

dex

Content

0x1A00

128

TxPDO

0x2000

0x01–

0x80

Output data

0x1A01

128

TxPDO

0x2001

0x01–

0x80

Diagnostic word (Low Byte)

0x1A02

128

TxPDO

0x2002

0x01–

0x80

Diagnostic word (High Byte)

0x1A03

128

TxPDO

0x2003

0x01–

0x80

Status of inputs
Status of input LED
State of outputs
Status of LED

0x1600

20

RxPDO

0x2100

0x01–

0x14

Input data

Information
Data with indices 2001 to 2003 is only updated by the PNOZmulti piece by
piece in each cycle. This may mean that interdependent data is inconsist-
ent. Updating all of the data can take up to 500 ms.

PNOZ mc2.1p/PNOZ mmc11p
All the objects (variables and parameters) that are relevant for these units are entered in
the object directory. Service Data Objects (SDOs) are used for read and write access.
The SDOs in the PNOZ mc2.1p, PNOZ mmc11p are integrated in an ESI file (Ethercat
Slave Information). The ESI file is incorporated in the EtherCAT Configurator for use of
SDOs in the PNOZ mc2.1p, PNOZ mmc11p.
The manufacturer-specific part of the object directory is structured as follows:

PDO

Size

Name

Index

Sub-Index

Content

0x1A00

20

TxPDO

0x2000

0x01–0x14

Output data

0x1A01

128

TxPDO

Configurable Configurable Default configuration of im-

portant SDOs

0x1600

20

RxPDO

0x2100

0x01–0x14

Input data

Information
Data with indices 2001 to 2003 is only updated by the PNOZmulti piece by
piece in each cycle. This may mean that interdependent data is inconsist-
ent. Updating all of the data can take up to 500 ms.

4.2.1.2