Safety valve

Bit/

DW

Message

Comment

Bit 0

Valve is not activated.

Bit 2

Valve is ready for reset.

Reset error messages on the reset input

Bit 8

Cannot switch on because, according to the feed-

back loop, the valve is already switched on.

Start attempt for open feedback loop

Bit 11 When the valve was switched on, the feedback loop

failed to open or opened too late.

Power-up monitoring time TOn exceeded,

feedback loop did not open during TOn

Bit 12 When the valve was switched off, the feedback loop

failed to close or closed too late.

Switch off monitoring time T0ff exceeded,

feedback loop did not close during TOff

Bit 13 Error caused by valve or feedback loop

Feedback loop closes when the valve is ac-

tivated