Operating Manual PNOZmulti communication interfaces
1001154-EN-13
16
Assignment of Byte 0 ... Byte 3
The current status of the virtual outputs configured for the fieldbus plus the current status of
the LED are always stored in Byte 0 ... Byte 3. All other information is stored in various ta-
bles (see Appendix).
Input area
The virtual inputs are defined by the Master and transferred to the PNOZmulti. Each input
has a number, e.g. input bit 4 of byte 1 has the number i12.
Byte
0
i7
i6
i5
i4
i3
i2
i1
i0
1
i15
i14
i13
i12
i11
i10
i9
i8
2
i23
i22
i21
i20
i19
i18
i17
i16
3
Reserved
Output area
The virtual outputs are defined in the PNOZmulti Configurator. Each output that is used is
given a number there, e.g. o0, o5... . The status of output o0 is stored in bit 0 of byte 0; the
status of output o5 is stored in bit 5 of byte 0 etc.
Byte
0
o7
o6
o5
o4
o3
o2
o1
o0
1
o15
o14
o13
o12
o11
o10
o9
o8
2
o23
o22
o21
o20
o19
o18
o17
o16
The status of the LEDs is stored in Byte 3 (output area only):
Bit 0 = 1:
LED OFAULT is lit or flashes
Bit 1 = 1:
LED IFAULT is lit or flashes
Bit 2 = 1:
LED FAULT is lit or flashes
Bit 3 = 1:
LED DIAG is lit
Bit 4 = 1:
LED RUN is lit
Bit 5:
Communication between the PNOZmulti and the fieldbus is working
Bit 6:
Reserved
Bit 7:
Reserved
4.1.4
- PNOZ mm0.1p PNOZ mm0.2p PNOZ mml1p PNOZ mml2p PNOZ mmc1p ETH PNOZ mmc2p seriell PNOZ mmc3p DP PNOZ mmc6p CAN PNOZ mmc4p DN PNOZ m1p base unit PNOZ m1p base unit coated version PNOZ m0p base unit not expandable PNOZ m2p base module press function PNOZ m3p base unit burner function PNOZ m1p ETH PNOZ m3p ETH PNOZ m0p ETH PNOZ m2p ETH PNOZ m1p ETH coated version PNOZ mi1p 8 input PNOZ mi1p 8 input coated version PNOZ mo1p 4 so PNOZ mo1p 4so coated version PNOZ mo3p 2so PNOZ mo2p 2n/o PNOZ mo2p 2n/o coated version PNOZ mo5p 4 n/o burner PNOZ mo4p 4n/o PNOZ mo4p 4n/o coated version PNOZ ml1p safe link 24VDC PNOZ ml2p safe link PDP PNOZ ms1p standstill / speed monitor PNOZ ms2p PNOZ ma1p 2 Analog Input PNOZ ms3p standstill / speed monitor PNOZms2p HTL PNOZ ma1p coated version PNOZ ml1p coated version PNOZ ms2p TTL coated version PNOZ ms3p HTL PNOZ ms2p TTL PNOZ ms3p TTL PNOZ mi2p 8 standard input PNOZ mc1p PNOZ mc1p coated version PNOZ mc0p Powersupply PNOZ mc5p Interbus PNOZ mc7p CC-Link coated version PNOZ mc7p CC-Link PNOZ mc6p CANopen coated version PNOZmc5.1p Interbus LWL / Fiberoptic PNOZ mc4p DeviceNet coated version PNOZ mc8p Ethernet IP / Modbus TCP PNOZ mc9p Profinet IO PNOZ mc3p Profibus 2 PNOZ mc8p coated version PNOZ mc6p CANopen 2 PNOZ mc4p DeviceNet 2 PNOZ mc2.1p EtherCAT 2 PNOZ mc10p SERCOS III PNOZ mc7p CC-Link 2 PNOZ mc6.1p CANopen 3