Pilz PNOZ mm0p 24VDC User Manual
Page 84

RS232/Ethernet interfaces
Operating Manual PNOZmulti communication interfaces
1001154-EN-13
84
Send virtual inputs to the PNOZmulti, request state of the virtual
outputs and LED status from the PNOZmulti
Request 0x14 Segment 0x02
The communication partner uses this request to send virtual inputs to the PNOZmulti in ex-
actly the same way as request 0x14 segment 0x01. It also requests the virtual outputs and
the LED status from the PNOZmulti .
The mask (Bytes 24 to 39) is used to determine which of the virtual inputs in a Byte are to
be set. For example, if only inputs i0 to i5 are to be set in Byte 8, 0x3F must be entered in
the mask in Byte 24.
Telegram
Byte
Request
Byte
Response
0
0x05
0
0x05
1
0x15
1
0x15
2
0x00
2
0x00
3
0x26
3
0x16
4
0x14
4
0x94
5
0x00
5
0x00
6
0x02
6
0x02
7
0x00
7
0x00
8
Virtual inputs
Input Byte 0:
i7 to i0
8
Virtual outputs
Output Byte 0:
o7 to o0
...
...
...
...
23
Virtual inputs
Input Byte 15:
i127 to i120
23
Virtual outputs
Output Byte 15:
o127 to o120
24
Mask
Mask Byte 0:
i7 to i0
24
LED status
...
...
25
BCC
39
Mask
Mask Byte 15:
i127 to i120
26
0x10
40
Control Byte
41
BCC
42
0x10
To LED status
5.7.2
- PNOZ mm0.1p PNOZ mm0.2p PNOZ mml1p PNOZ mml2p PNOZ mmc1p ETH PNOZ mmc2p seriell PNOZ mmc3p DP PNOZ mmc6p CAN PNOZ mmc4p DN PNOZ m1p base unit PNOZ m1p base unit coated version PNOZ m0p base unit not expandable PNOZ m2p base module press function PNOZ m3p base unit burner function PNOZ m1p ETH PNOZ m3p ETH PNOZ m0p ETH PNOZ m2p ETH PNOZ m1p ETH coated version PNOZ mi1p 8 input PNOZ mi1p 8 input coated version PNOZ mo1p 4 so PNOZ mo1p 4so coated version PNOZ mo3p 2so PNOZ mo2p 2n/o PNOZ mo2p 2n/o coated version PNOZ mo5p 4 n/o burner PNOZ mo4p 4n/o PNOZ mo4p 4n/o coated version PNOZ ml1p safe link 24VDC PNOZ ml2p safe link PDP PNOZ ms1p standstill / speed monitor PNOZ ms2p PNOZ ma1p 2 Analog Input PNOZ ms3p standstill / speed monitor PNOZms2p HTL PNOZ ma1p coated version PNOZ ml1p coated version PNOZ ms2p TTL coated version PNOZ ms3p HTL PNOZ ms2p TTL PNOZ ms3p TTL PNOZ mi2p 8 standard input PNOZ mc1p PNOZ mc1p coated version PNOZ mc0p Powersupply PNOZ mc5p Interbus PNOZ mc7p CC-Link coated version PNOZ mc7p CC-Link PNOZ mc6p CANopen coated version PNOZmc5.1p Interbus LWL / Fiberoptic PNOZ mc4p DeviceNet coated version PNOZ mc8p Ethernet IP / Modbus TCP PNOZ mc9p Profinet IO PNOZ mc3p Profibus 2 PNOZ mc8p coated version PNOZ mc6p CANopen 2 PNOZ mc4p DeviceNet 2 PNOZ mc2.1p EtherCAT 2 PNOZ mc10p SERCOS III PNOZ mc7p CC-Link 2 PNOZ mc6.1p CANopen 3