beautypg.com

Gf-122 aerco xpc gateway, Figure 3-15. bms ii sample network diagrams, Bms ii connected to xpc port 2 – AERCO XPC GATEWAY Communications User Manual

Page 63: Bms ii connected to xpc port 1a

background image

GF-122 AERCO XPC GATEWAY

63

NOTE:

PORT 1a CONNECTIONS WILL DEPEND ON THE
AVAILABLE PORTS ON THE BAS BEING USED.

IF THE BAS CONTAINS A 4-WIRE RS485 PORT, SEE
DETAIL “A”.

IF THE BAS CONTAINS ONLY A RS232 PORT, A
RS485-TO-RS232 CONVERTER WILL BE REQUIRED.

RXD
TXD

GND

+(B)
-(A)

SHLD

TO C-MORE

OR MODULEX

BOILERS

CONTROLLED

VIA RS485

NETWORK

BMS II

JP6

JP5

RS232

XPC GATEWAY

PORT

1a

NET +

NET -

SHLD

TX

DTR

DCD
GND

EIA-232

EIA-485

2W

4W

TO BAS

(SEE NOTE)

PORT

2

RX

RS485

T+

R-

R+

T-

SHIELD

4-WIR

E RS

485

POR

T

DETAIL “A”

BMS II CONNECTED TO XPC PORT 2

NOTE:

PORT 2 CONNECTIONS AND JUMPER POSITIONS
WILL DEPEND ON THE AVAILABLE PORTS ON THE
BAS BEING USED. SEE DETAIL “A”.

XPC GATEWAY

PORT

1a

NET +

NET -

SHLD

EIA-232

EIA-485

2W

4W

TO BAS

(SEE NOTE)

PORT

2

SE

E NO

TE

JUMPERS

RS485-TO- RS232

CONVERTER

RS232

RS485

2W

4W

232

Net +

Net -

N/C

N/C

Tx +

Tx

Tx -

Rx

DTR

Rx -

DCD

SIGNAL GROUND

Rx +

Port 2

DETAIL “A”

B+

A-

GND

RXD

TXD

GND

RXD
TXD

GND

+(B)
-(A)

SHLD

TO C-MORE

OR MODULEX

BOILERS

CONTROLLED

VIA RS485

NETWORK

BMS II

JP6

JP5

JP7

+12V

ISO

12V

ISO

GND

BMS II CONNECTED TO XPC PORT 1a

Figure 3-15. BMS II Sample Network Diagrams