GF-122 AERCO XPC GATEWAY
133
Modbus-To-BACnet Protocol Mapping
1 BMS/BMS II, 8 C-More Boilers (Continued)
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
BACnet
Type:ID
Blr Addr 4
01-Fire Rate Out
boilerstate_4
30009/4
AV:70
02-Active Setpoint
effectsetpt_4
30017/4
AV:71
03-Net Remote Setpt
setpt_4
40001/4
AV:72
05-Fire Rate In
boilerload_4
30018/4
AV:73
06-Outlet Temp
localsuptemp_4
30003/4
AV:65
07-Display Code
dispcode_4
30001/4
AV:66
08-Unit Status
unitstat_4
30002/4
AV:67
09-Run Cycles
runcycles_4
30012-30013/4
AV:68
10-Run Hours
runhours_4
30014-30015/4
AV:69
Deg F or Deg C
m114_4
BV:10
Use Temp Scaling
m101_4
BV:11
Blr Addr 5
01-Fire Rate Out
boilerstate_5
30009/5
AV:80
02-Active Setpoint
effectsetpt_5
30017/5
AV:81
03-Net Remote Setpt
setpt_5
40001/5
AV:82
05-Fire Rate In
boilerload_5
30018/5
AV:74
06-Outlet Temp
localsuptemp_5
30003/5
AV:75
07-Display Code
dispcode_5
30001/5
AV:76
08-Unit Status
unitstat_5
30002/5
AV:77
09-Run Cycles
runcycles_5
30012-30013/5
AV:78
10-Run Hours
runhours_5
30014-30015/5
AV:79
Deg F or Deg C
m114_5
BV:12
Use Temp Scaling
m101_5
BV:13
Blr Addr 6
01-Fire Rate Out
boilerstate_6
30009/6
AV:90
02-Active Setpoint
effectsetpt_6
30017/6
AV:91
03-Net Remote Setpt
setpt_6
40001/6
AV:92
05-Fire Rate In
boilerload_6
30018/6
AV:84
06-Outlet Temp
localsuptemp_6
30003/6
AV:85
07-Display Code
dispcode_6
30001/6
AV:86
08-Unit Status
unitstat_6
30002/6
AV:87
09-Run Cycles
runcycles_6
30012-30013/6
AV:88
10-Run Hours
runhours_6
30014-30015/6
AV:89
Deg F or Deg C
m114_6
BV:14
Use Temp Scaling
m101_6
BV:15
Page 2 of 4