Gateway communications manual – AERCO XPC GATEWAY Communications User Manual
Page 134
![background image](/manuals/659328/134/background.png)
GATEWAY COMMUNICATIONS MANUAL
134
Modbus-To-BACnet Protocol Mapping
1 BMS/BMS II, 8 C-More Boilers (Continued)
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
BACnet
Type:ID
Blr Addr 7
01-Fire Rate Out
boilerstate_7
30009/7
AV:100
02-Active Setpoint
effectsetpt_7
30017/7
AV:101
03-Net Remote Setpt
setpt_7
40001/7
AV:102
05-Fire Rate In
boilerload_7
30018/7
AV:94
06-Outlet Temp
localsuptemp_7
30003/7
AV:95
07-Display Code
dispcode_7
30001/7
AV:96
08-Unit Status
unitstat_7
30002/7
AV:97
09-Run Cycles
runcycles_7
30012-30013/7
AV:98
10-Run Hours
runhours_7
30014-30015/7
AV:99
Deg F or Deg C
m114_7
BV:16
Use Temp Scaling
m101_7
BV:17
Blr Addr 8
01-Fire Rate Out
boilerstate_8
30009/8
AV:110
02-Active Setpoint
effectsetpt_8
30017/8
AV:111
03-Net Remote Setpt
setpt_8
40001/8
AV:112
05-Fire Rate In
boilerload_8
30018/8
AV:104
06-Outlet Temp
localsuptemp_8
30003/8
AV:105
07-Display Code
dispcode_8
30001/8
AV:106
08-Unit Status
unitstat_8
30002/8
AV:107
09-Run Cycles
runcycles_8
30012-30013/8
AV:108
10-Run Hours
runhours_8
30014-30015/8
AV:109
Deg F or Deg C
m114_8
BV:18
Use Temp Scaling
m101_8
BV:19