Modbus-To-BACnet Protocol Mapping

1 BMS/BMS II, 8 C-More Boilers (Continued)

Equipment

Point Name

Name

Modbus Data

Addr/Unit Addr

Read

Only Enabled

BACnet

Type:ID

Blr Addr 7

01-Fire Rate Out

boilerstate_7

30009/7

AV:100

02-Active Setpoint

effectsetpt_7

30017/7

AV:101

03-Net Remote Setpt

setpt_7

40001/7

AV:102

05-Fire Rate In

boilerload_7

30018/7

AV:94

06-Outlet Temp

localsuptemp_7

30003/7

AV:95

07-Display Code

dispcode_7

30001/7

AV:96

08-Unit Status

unitstat_7

30002/7

AV:97

09-Run Cycles

runcycles_7

30012-30013/7

AV:98

10-Run Hours

runhours_7

30014-30015/7

AV:99

Deg F or Deg C

m114_7

BV:16

Use Temp Scaling

m101_7

BV:17

Blr Addr 8

01-Fire Rate Out

boilerstate_8

30009/8

AV:110

02-Active Setpoint

effectsetpt_8

30017/8

AV:111

03-Net Remote Setpt

setpt_8

40001/8

AV:112

05-Fire Rate In

boilerload_8

30018/8

AV:104

06-Outlet Temp

localsuptemp_8

30003/8

AV:105

07-Display Code

dispcode_8

30001/8

AV:106

08-Unit Status

unitstat_8

30002/8

AV:107

09-Run Cycles

runcycles_8

30012-30013/8

AV:108

10-Run Hours

runhours_8

30014-30015/8

AV:109

Deg F or Deg C

m114_8

BV:18

Use Temp Scaling

m101_8

BV:19