Gateway communications manual – AERCO XPC GATEWAY Communications User Manual
Page 190

GATEWAY COMMUNICATIONS MANUAL
190
Table 13 Burner Management Module (BMM) Error Codes
CODE
DESCRIPTION
EFFECT
CORRECTION
RESET
1
High Limit (STB)
Thermostat activated
All burners turned OFF
and Pump ON at
maximum speed.
Check FlowSensor thermal connection to
boiler.
MANUAL - push reset
switch when temperature
goes below limit.
2
Low Gas Pressure
All burners turned OFF .
Check gas pressure or gas pressure
switch.
AUTOMATIC - when gas
pressure switch closes.
4
No flame detected at
burner start
Burner control lockout.
Check flame rod or combustion.
MANUAL - push reset
switch or cycle power.
5
Flame loss during run.
Ignition retry.
Check combustion and wiring.
MANUAL - push reset
switch or cycle power.
6
High outlet temperature.
FlowSensor temperature >
203°F.
All burners turned OFF
and Pump ON at
maximum speed.
Check Flow Sensor or system pump
AUTOMATIC - when
FlowSensor < 176°F.
10
Internal Failure
Ignition is inhibited.
Contact Factory for new BCM.
MANUAL - cycle the
power.
11
Flame signal detected
before ignition.
Ignition is inhibited.
Disconnect flame rod wire from BMM. If
problem goes away change flame rod
and/or wire. If problem does not go
away change BMM.
MANUAL - push reset
switch or cycle power.
12
FlowSensor fault.
All burners turned OFF.
Check flow sensor or wiring.
AUTOMATIC
13
Aux Sensor fault
The boiler will operate
from the FlowSensor
without the AuxSensor.
Check aux sensor or wiring.
AUTOMATIC