Gf-122 aerco xpc gateway – AERCO XPC GATEWAY Communications User Manual
Page 179

GF-122 AERCO XPC GATEWAY
179
Modbus-To-LonWorks Protocol Mapping
1 BMS II, 4 MLX Boilers
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
SNVT
#
SNVT NAME
SNVT
Element
#
Direction
Prio Auth Ack
BMS Addr 128
01-Fire Rate Out
boilerstate_5
30005/128
1
nvoBlrState
incremental
count (9)
0
Output (non-
polled)
02-Header Set
Temp
effectsetpt_5
30006/128
2
nvoEffSetpt
incremental
count (9)
0
Output (non-
polled)
03-Net Header Set
Temp
setpt_5
40005/128
3
nviSetpt
incremental
count (9)
0
Input (non-
polling)
04-Header Temp
localsuptemp_5
30002/128
4
nvoLocSupTmp
incremental
count (9)
0
Output (non-
polled)
05-Outside Air
Temp
localoatemp_5
30003/128
5
nvoLocOATmp
incremental
count (9)
0
Output (non-
polled)
06-Display Code
dispcode_5
30011/128
6
nvoDispCode
incremental
count (9)
0
Output (non-
polled)
07-Num Boilers
Fired
blrfired_5
30008/128
7
nvoBlrsFired
incremental
count (9)
0
Output (non-
polled)
08-Num Boilers
Online
blronline_5
30009/128
8
nvoBlrsOnline
incremental
count (9)
0
Output (non-
polled)
09-Last Blr Fired
blrlast_5
30017/128
9
nvoLastBlrFired
incremental
count (9)
0
Output (non-
polled)
18-Net Blr 1 Status
blr9stat_5
30026/128
29
nvoNetBlr1Stat
incremental
count (9)
0
Output (non-
polled)
19-Net Blr 2 Status
blr10stat_5
30027/128
30
nvoNetBlr2Stat
incremental
count (9)
0
Output (non-
polled)
20-Net Blr 3 Status
blr11stat_5
30028/128
31
nvoNetBlr3Stat
incremental
count (9)
0
Output (non-
polled)
21-Net Blr 4 Status
blr12stat_5
30029/128
32
nvoNetBlr4Stat
incremental
count (9)
0
Output (non-
polled)
Use Metric
Conversion
m101_5
0
disabled NV
(0)
1
Input (non-
polling)
Page 1 of 3