Gateway communications manual – AERCO XPC GATEWAY Communications User Manual
Page 146
![background image](/manuals/659328/146/background.png)
GATEWAY COMMUNICATIONS MANUAL
146
Modbus-To-N2 Protocol Mapping
1 BMS/BMS II, 8 C-More Boilers
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
Type
N2
ID
Blr Addr 1
01-Fire Rate Out
boilerstate_1
30009/1
data float
1
02-Active Setpoint
effectsetpt_1
30017/1
data float
2
03-Net Remote Setpt
setpt_1
40001/1
data float
3
05-Fire Rate In
boilerload_1
30018/1
data float
5
06-Outlet Temp
localsuptemp_1
30003/1
data float
6
07-Display Code
dispcode_1
30001/1
data float
7
08-Unit Status
unitstat_1
30002/1
data float
8
09-Run Cycles
runcycles_1
30012-30013/1
data float
9
10-Run Hours
runhours_1
30014-30015/1
data float
10
Deg F or Deg C
m114_1
binary out
1
Use Temp Scaling
m101_1
binary out
2
Blr Addr 2
01-Fire Rate Out
boilerstate_2
30009/2
data float
11
02-Active Setpoint
effectsetpt_2
30017/2
data float
12
03-Net Remote Setpt
setpt_2
40001/2
data float
13
05-Fire Rate In
boilerload_2
30018/2
data float
15
06-Outlet Temp
localsuptemp_2
30003/2
data float
16
07-Display Code
dispcode_2
30001/2
data float
17
08-Unit Status
unitstat_2
30002/2
data float
18
09-Run Cycles
runcycles_2
30012-30013/2
data float
19
10-Run Hours
runhours_2
30014-30015/2
data float
20
Deg F or Deg C
m114_2
binary out
3
Use Temp Scaling
m101_2
binary out
4
Blr Addr 3
01-Fire Rate Out
boilerstate_3
30009/3
data float
21
02-Active Setpoint
effectsetpt_3
30017/3
data float
22
03-Net Remote Setpt
setpt_3
40001/3
data float
23
05-Fire Rate In
boilerload_3
30018/3
data float
25
06-Outlet Temp
localsuptemp_3
30003/3
data float
26
07-Display Code
dispcode_3
30001/3
data float
27
08-Unit Status
unitstat_3
30002/3
data float
28
09-Run Cycles
runcycles_3
30012-30013/3
data float
29
10-Run Hours
runhours_3
30014-30015/3
data float
30
Deg F or Deg C
m114_3
binary out
5
Use Temp Scaling
m101_3
binary out
6
Page 1 of 4