Gateway communications manual – AERCO XPC GATEWAY Communications User Manual

Page 148

background image

GATEWAY COMMUNICATIONS MANUAL

148

Modbus-To-N2 Protocol Mapping

1 BMS/BMS II, 8 C-More Boilers (Continued)

Equipment

Point Name

Name

Modbus Data

Addr/Unit Addr

Read

Only Enabled

Type

N2

ID

Blr Addr 7

01-Fire Rate Out

boilerstate_7

30009/7

data float

61

02-Active Setpoint

effectsetpt_7

30017/7

data float

62

03-Net Remote Setpt

setpt_7

40001/7

data float

63

05-Fire Rate In

boilerload_7

30018/7

data float

65

06-Outlet Temp

localsuptemp_7

30003/7

data float

66

07-Display Code

dispcode_7

30001/7

data float

67

08-Unit Status

unitstat_7

30002/7

data float

68

09-Run Cycles

runcycles_7

30012-30013/7

data float

69

10-Run Hours

runhours_7

30014-30015/7

data float

70

Deg F or Deg C

m114_7

binary out

13

Use Temp Scaling

m101_7

binary out

14

Blr Addr 8

01-Fire Rate Out

boilerstate_8

30009/8

data float

71

02-Active Setpoint

effectsetpt_8

30017/8

data float

72

03-Net Remote Setpt

setpt_8

40001/8

data float

73

05-Fire Rate In

boilerload_8

30018/8

data float

75

06-Outlet Temp

localsuptemp_8

30003/8

data float

76

07-Display Code

dispcode_8

30001/8

data float

77

08-Unit Status

unitstat_8

30002/8

data float

78

09-Run Cycles

runcycles_8

30012-30013/8

data float

79

10-Run Hours

runhours_8

30014-30015/8

data float

80

Deg F or Deg C

m114_8

binary out

15

Use Temp Scaling

m101_8

binary out

16