GATEWAY COMMUNICATIONS MANUAL

192

Table 13 Burner Management Module (BMM) Error Codes - Continued

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

24

Fan speed out of control: It
doesn't reach pre-purge
speed within 30 seconds.

Ignition retry after 60
second delay and failure
remains until we have a
successful burner
operation.

Check fan wiring.

AUTOMATIC/MANUAL

26

Fan speed out of control: It
doesn't stop within 30
seconds after turned OFF.

Ignition is inhibited.

Check fan wiring.

AUTOMATIC

27

Air flow failure during
ignition.

Restart pre-purge timer.
The failure remains until
we have a successful
burner operation.

Check fan and wiring. Check air proving
switch and wiring.

AUTOMATIC

30

Settings Corrupted

Ignition is inhibited. Pump
runs for 5 min at max
speed.

Re-program the settings. Contact
Factory

MANUAL - cycle the power
or send reset message.

32

Line voltage too low. (<96
VAC)

Wait for proper line
voltage. (>102 VAC)

Check input voltage else try another
BMM.

AUTOMATIC

40

Low Water Flow. Low
water flow switch activated.

Burners turned OFF.

Check water flow or check switch.

AUTOMATIC