Gf-122 aerco xpc gateway – AERCO XPC GATEWAY Communications User Manual
Page 145
GF-122 AERCO XPC GATEWAY
145
Modbus-To-N2 Protocol Mapping
1 BMS/BMS II, 4 C-More Boilers (Continued)
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
Type
N2
ID
Blr Addr 4
01-Fire Rate Out
boilerstate_4
30009/4
data float
31
02-Active Setpoint
effectsetpt_4
30017/4
data float
32
03-Net Remote Setpt
setpt_4
40001/4
data float
33
05-Fire Rate In
boilerload_4
30018/4
data float
35
06-Outlet Temp
localsuptemp_4
30003/4
data float
36
07-Display Code
dispcode_4
30001/4
data float
37
08-Unit Status
unitstat_4
30002/4
data float
38
09-Run Cycles
runcycles_4
30012-30013/4
data float
39
10-Run Hours
runhours_4
30014-30015/4
data float
40
Deg F or Deg C
m114_4
binary out
7
Use Temp Scaling
m101_4
binary out
8
BMS Addr 128
01-Fire Rate Out
boilerstate_5
30005/128
data float
41
02-Header Set Temp
effectsetpt_5
30006/128
data float
42
03-Net Header Set Temp
setpt_5
40005/128
data float
43
04-Header Temp
localsuptemp_5
30002/128
data float
44
05-Outside Air Temp
localoatemp_5
30003/128
data float
45
06-Display Code
dispcode_5
30011/128
data float
46
07-Num Boilers Fired
blrfired_5
30008/128
data float
47
08-Num Boilers Online
blronline_5
30009/128
data float
48
09-Last Blr Fired
blrlast_5
30017/128
data float
49
10-Boiler 1 Status
blr1stat_5
30018/128
data float
50
11-Boiler 2 Status
blr2stat_5
30019/128
data float
51
12-Boiler 3 Status
blr3stat_5
30020/128
data float
52
13-Boiler 4 Status
blr4stat_5
30021/128
data float
53
14-Boiler 5 Status
blr5stat_5
30022/128
data float
54
15-Boiler 6 Status
blr6stat_5
30023/128
data float
55
16-Boiler 7 Status
blr7stat_5
30024/128
data float
56
17-Boiler 8 Status
blr8stat_5
30025/128
data float
57
18-Net Blr 1 Status
blr9stat_5
30026/128
data float
58
19-Net Blr 2 Status
blr10stat_5
30027/128
data float
59
20-Net Blr 3 Status
blr11stat_5
30028/128
data float
60
21-Net Blr 4 Status
blr12stat_5
30029/128
data float
61
Use Metric Conversion
m101_5
binary out
9
Page 2 of 2