AERCO Float and Thermostatic Traps Series X User Manual
Float and thermostatic traps series h, c and x, Hoffman specialty, Warning
Hoffman Specialty
Installation & Maintenance
Instructions
HS-222(E)
Float and Thermostatic Traps
Series H, C and X
• Before using product, read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application,
installation, and maintenance of steam systems in accordance with all applicable codes
and ordinances.
• To prevent serious burns, wear heat resistant gloves when opening and closing steam
valves, or handling hot equipment.
• To prevent serious burns, the internal pressure of the trap must be 0 psi (0 bar) before
servicing.
• To prevent serious personal injury from steam pipe blow down, connect a temporary
pipe between the steam pipe opening and a drain, or stand at least 100 ft. (30 m) from
the front of the pipe opening.
• To prevent property damage, personal injury, or death, cap off the gate valves if they are
not connected to a drain and when they are not in use for test or pressure relief.
Failure to follow this warning could cause property damage, personal injury or death.
!
WARNING
CAUTION
WARNING
®
Series C
1
1
⁄
4
& 1
1
⁄
2
NPT
Series C
2 NPT
Series X
2 NPT
Series C
2
1
⁄
2
NPT
Series H
Ratings
Maximum
Max. Operating
NPT Size - in.
Temperature
Pressure
°F (°C)
psig (bar)
3
⁄
4
”, 1” and 1
1
⁄
4
” H
406 (208)
175 (12.1)
1
1
⁄
4
” C and All 1
1
⁄
2
” - 2
1
⁄
2
”
377 (192)