GF-122 AERCO XPC GATEWAY

187

Table 11 C-More Controller Status and Fault Messages –Cont.

Code

MESSAGE

DESCRIPTION

37

IGNITION BOARD COMM
FAULT

Communication fault between the Ignition board and the CPU
board.

38

WAIT

Prompts the operator to wait.

39

DIRECT DRIVE

SIGNAL FAULT

The direct drive signal is not present or is out of range.

40

REMOTE SETPT

SIGNAL FAULT

The remote setpoint signal is not present or is out of range.

41

OUTDOOR TEMP

SENSOR FAULT

The temperature measured by the Outdoor Air Sensor is out of
range.

42

OUTLET TEMP

SENSOR FAULT

The temperature measured by the Outlet Sensor is out of
range.

43

FFWD TEMP

SENSOR FAULT

The temperature measured by the FFWD Sensor is out of
range.

44

HIGH WATER

TEMPERATURE

The temperature measured by the Outlet Sensor exceeded the
Temp Hi Limit setting.

45

LINE VOLTAGE

OUT OF PHASE

The High AC voltage is out of phase from the low AC voltage.

46

STEPPER MOTOR

FAILURE

The stepper motor failed to move the valve to the desired
position.

47

SETPT LIMITING ACTIVE

Setpoint temperature has exceeded the maximum allowable
setting.

48

MODBUS COMM FAULT

The RS485 (Modbus) network information is not present or is
corrupted.