Gf-122 aerco xpc gateway – AERCO XPC GATEWAY Communications User Manual
Page 141
GF-122 AERCO XPC GATEWAY
141
Modbus-To-BACnet Protocol Mapping
1 BMS II, 4 MLX Boilers
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
BACnet
Type:ID
BMS Addr 128
01-Fire Rate Out
boilerstate_5
30005/128
AV:31
02-Header Set Temp
effectsetpt_5
30006/128
AV:32
03-Net Header Set Temp
setpt_5
40005/128
AV:33
04-Header Temp
localsuptemp_5
30002/128
AV:34
05-Outside Air Temp
localoatemp_5
30003/128
AV:35
06-Display Code
dispcode_5
30011/128
AV:36
07-Num Boilers Fired
blrfired_5
30008/128
AV:37
08-Num Boilers Online
blronline_5
30009/128
AV:38
09-Last Blr Fired
blrlast_5
30017/128
AV:39
18-Net Blr 1 Status
blr9stat_5
30026/128
AV:26
19-Net Blr 2 Status
blr10stat_5
30027/128
AV:27
20-Net Blr 3 Status
blr11stat_5
30028/128
AV:47
21-Net Blr 4 Status
blr12stat_5
30029/128
AV:49
Use Metric Conversion
m101_5
BV:9
Mlx Addr 1
01-Act Mod Lev
boilerstate_1
41009/1
AV:134
02-Target Setpoint
effectsetpt_1
41019/1
AV:135
03-Req Outlet Temp
setpt_1
41005/1
AV:136
04-Net Direct Drive
boilercmd_1
40002/1
AV:137
05-Mod Lev In
boilerload_1
41201/1
AV:138
06-Flow Sens Temp
localsuptemp_1
41003/1
AV:139
07-Display Code
dispcode_1
30001/1
AV:140
11-Error Code
errcode_1
40001/1
AV:1
08-Unit Status
unitstat_1
30002/1
AV:141
09-Ret Flow Temp
returntemp_1
41004/1
AV:2
Mlx Addr 2
01-Act Mod Lev
boilerstate_2
41009/2
AV:144
02-Target Setpoint
effectsetpt_2
41019/2
AV:145
03-Req Outlet Temp
setpt_2
41005/2
AV:146
04-Net Direct Drive
boilercmd_2
40002/2
AV:147
05-Mod Lev In
boilerload_2
41201/2
AV:148
06-Flow Sens Temp
localsuptemp_2
41003/2
AV:149
07-Display Code
dispcode_2
30001/2
AV:150
11-Error Code
errcode_2
40001/2
AV:4
08-Unit Status
unitstat_2
30002/2
AV:151
09-Ret Flow Temp
returntemp_2
41004/2
AV:5