Modbus-To-BACnet Protocol Mapping

1 BMS II, 4 MLX Boilers

Equipment

Point Name

Name

Modbus Data

Addr/Unit Addr

Read

Only Enabled

BACnet

Type:ID

BMS Addr 128

01-Fire Rate Out

boilerstate_5

30005/128

AV:31

02-Header Set Temp

effectsetpt_5

30006/128

AV:32

03-Net Header Set Temp

setpt_5

40005/128

AV:33

04-Header Temp

localsuptemp_5

30002/128

AV:34

05-Outside Air Temp

localoatemp_5

30003/128

AV:35

06-Display Code

dispcode_5

30011/128

AV:36

07-Num Boilers Fired

blrfired_5

30008/128

AV:37

08-Num Boilers Online

blronline_5

30009/128

AV:38

09-Last Blr Fired

blrlast_5

30017/128

AV:39

18-Net Blr 1 Status

blr9stat_5

30026/128

AV:26

19-Net Blr 2 Status

blr10stat_5

30027/128

AV:27

20-Net Blr 3 Status

blr11stat_5

30028/128

AV:47

21-Net Blr 4 Status

blr12stat_5

30029/128

AV:49

Use Metric Conversion

m101_5

BV:9

Mlx Addr 1

01-Act Mod Lev

boilerstate_1

41009/1

AV:134

02-Target Setpoint

effectsetpt_1

41019/1

AV:135

03-Req Outlet Temp

setpt_1

41005/1

AV:136

04-Net Direct Drive

boilercmd_1

40002/1

AV:137

05-Mod Lev In

boilerload_1

41201/1

AV:138

06-Flow Sens Temp

localsuptemp_1

41003/1

AV:139

07-Display Code

dispcode_1

30001/1

AV:140

11-Error Code

errcode_1

40001/1

AV:1

08-Unit Status

unitstat_1

30002/1

AV:141

09-Ret Flow Temp

returntemp_1

41004/1

AV:2

Mlx Addr 2

01-Act Mod Lev

boilerstate_2

41009/2

AV:144

02-Target Setpoint

effectsetpt_2

41019/2

AV:145

03-Req Outlet Temp

setpt_2

41005/2

AV:146

04-Net Direct Drive

boilercmd_2

40002/2

AV:147

05-Mod Lev In

boilerload_2

41201/2

AV:148

06-Flow Sens Temp

localsuptemp_2

41003/2

AV:149

07-Display Code

dispcode_2

30001/2

AV:150

11-Error Code

errcode_2

40001/2

AV:4

08-Unit Status

unitstat_2

30002/2

AV:151

09-Ret Flow Temp

returntemp_2

41004/2

AV:5