GF-122 AERCO XPC GATEWAY

3

Foreword

The AERCO XPC (Extended Protocol Converter) allows a Building Automation Systems (BAS) or
Energy Management System (EMS) utilizing BACnet, Johnson N2 or LonWorks protocol to
communicate with AERCO boilers and water heaters which utilize Modbus.

The AERCO XPC Gateway can monitor and control up to 300 points. Each XPC is individually
programmed to your specific needs.

The information provided in this document is divided into an Introduction followed by three (3) parts:

Introduction – An introduction to and general description of the AERCO XPC Gateway.

Part

I

- Provides a top-level description of the AERCO XPC Gateway features and capabilities.

It also includes detailed set-up and programming instructions to interface the XPC
Gateway to the AERCO equipment to be monitored or controlled on the network.

Part

II

- Provides the set-up and programming instructions to interface the AERCO XPC

Gateway to a Building Automation System (BAS) or Energy Management System (EMS)
which utilizes BACnet, Johnson N2 or LonWorks protocol.

Part

III

– Provides the protocol mapping points for the standard configurations which can be

monitored or controlled.

PHRASES, ABBREVIATIONS & ACRONYMS

The phrases, abbreviations and acronyms used in this document are listed in the following table.

Phrases, Abbreviations and Acronyms

Phrase, Abbreviation

or Acronym

Meaning

ARCnet

Attached Resource Computer network. This is a Local Area Network (LAN)
similar to Ethernet.

ASCII

American Standard Code for Information Interchange

ASHRAE

American Society of Heating, Refrigerating and Air Conditioning Engineers

BACnet

Building Automation and Control network. Protocol developed by ASHRAE.

BAS

Building Automation System, often used interchangeably with EMS (see
below)

Baud Rate

Symbol rate, or simply the number of distinct symbol changes (signaling
events) transmitted per second. It is not equal to bits per second, unless
each symbol is 1 bit long.

BCM

Boiler Control Module used in a Modulex (MLX) Boiler

BMS (BMS II)

Boiler Management System (Boiler Management System II)

Bias Resistors

A pair of resistors used to force the communication line to a definite logic
state so that noise is not picked up as invalid data during communication.

C-More Controller
(or Control Box)

A control system developed by AERCO and currently used in all Benchmark
and KC Series product lines.

DIP

Dual In-Line Package