Gf-122 aerco xpc gateway – AERCO XPC GATEWAY Communications User Manual
Page 183
![background image](/manuals/659328/183/background.png)
GF-122 AERCO XPC GATEWAY
183
Modbus-To-LonWorks Protocol Mapping
4 ECS Heaters
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
SNVT
#
SNVT NAME
SNVT
Element
#
Direction
Prio Auth Ack
E Valve
Addr 29
01-Cntl Output
Signal
boilerstate_1
30004/29
201
nvoEcsState29
incremental
count (9)
0
Output (non-
polled)
02-Setpoint
effectsetpt_1
30006/29
202
nvoEcsSetpt29
incremental
count (9)
0
Output (non-
polled)
03-RmSetpt
rmsetpt_1
40027/29
203
nviEcsSetptRq29
incremental
count (9)
0
Input (non-
polling)
04-Outlet Temp
localsuptemp_1
30002/29
204
nvoEcsSupTmp29
incremental
count (9)
0
Output (non-
polled)
05-FBk Sensor
Temp
localrettemp_1
30290/29
205
nvoEcsRetTmp29
incremental
count (9)
0
Output (non-
polled)
06-Over Temp
Alarm
unitstat_1
30075/29
206
nvoEcsStat29
incremental
count (9)
0
Output (non-
polled)
07-Flow Rate
flowrate_1
30291/29
207
nvoEcsFlow29
incremental
count (9)
0
Output (non-
polled)
Use Metric
Conversion
m101_1
0
disabled NV
(0)
1
Output (non-
polled)
E Valve
Addr 30
01-Cntl Output
Signal
boilerstate_2
30004/30
211
nvoEcsState30
incremental
count (9)
0
Output (non-
polled)
02-Setpoint
effectsetpt_2
30006/30
212
nvoEcsSetpt30
incremental
count (9)
0
Output (non-
polled)
03-RmSetpt
rmsetpt_2
40027/30
213
nviEcsSetptRq30
incremental
count (9)
0
Input (non-
polling)
04-Outlet Temp
localsuptemp_2
30002/30
214
nvoEcsSupTmp30
incremental
count (9)
0
Output (non-
polled)
05-FBk Sensor
Temp
localrettemp_2
30290/30
215
nvoEcsRetTmp30
incremental
count (9)
0
Output (non-
polled)
06-Over Temp
Alarm
unitstat_2
30075/30
216
nvoEcsStat30
incremental
count (9)
0
Output (non-
polled)
07-Flow Rate
flowrate_2
30291/30
217
nvoEcsFlow30
incremental
count (9)
0
Output (non-
polled)
Use Metric
Conversion
m101_2
0
disabled NV
(0)
1
Output (non-
polled)
Page 1 of 2