Gf-122 aerco xpc gateway – AERCO XPC GATEWAY Communications User Manual
Page 181

GF-122 AERCO XPC GATEWAY
181
Modbus-To-LonWorks Protocol Mapping 1 BMS II, 4 MLX Boilers (Continued)
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
SNVT
#
SNVT NAME
SNVT
Element
#
Direction
Prio Auth Ack
Mlx Addr 3
01-Act Mod Lev
boilerstate_3
41009/3
181
nvoMlxState3
incremental
count (9)
0
Output (non-
polled)
02-Target Setpoint
effectsetpt_3
41019/3
182
nvoMlxSetpt3
incremental
count (9)
0
Output (non-
polled)
03-Req Outlet
Temp
setpt_3
41005/3
183
nviMlxSetptRq3
incremental
count (9)
0
Input (non-
polling)
04-Net Direct Drive
boilercmd_3
40002/3
184
nviMlxCmd3
incremental
count (9)
0
Input (non-
polling)
05-Mod Lev In
boilerload_3
41201/3
185
nvoMlxLoad3
incremental
count (9)
0
Output (non-
polled)
06-Flow Sens
Temp
localsuptemp_3
41003/3
186
nvoMlxSupTmp3
incremental
count (9)
0
Output (non-
polled)
07-Display Code
dispcode_3
30001/3
188
nvoMlxDispCode3
incremental
count (9)
0
Output (non-
polled)
11-Error Code
errcode_3
40001/3
189
nvoMlxErrCode3
51
0
Output (non-
polled)
08-Unit Status
unitstat_3
30002/3
190
nvoMlxStat3
incremental
count (9)
0
Output (non-
polled)
09-Ret Flow Temp
returntemp_3
41004/3
187
nvoMlxRetTmp3
incremental
count (9)
0
Output (non-
polled)
Mlx Addr 4
01-Act Mod Lev
boilerstate_4
41009/4
191
nvoMlxState4
incremental
count (9)
0
Output (non-
polled)
02-Target Setpoint
effectsetpt_4
41019/4
192
nvoMlxSetpt4
incremental
count (9)
0
Output (non-
polled)
03-Req Outlet
Temp
setpt_4
41005/4
193
nviMlxSetptRq4
incremental
count (9)
0
Input (non-
polling)
04-Net Direct Drive
boilercmd_4
40002/4
194
nviMlxCmd4
incremental
count (9)
0
Input (non-
polling)
05-Mod Lev In
boilerload_4
41201/4
195
nvoMlxLoad4
incremental
count (9)
0
Output (non-
polled)
06-Flow Sens
Temp
localsuptemp_4
41003/4
196
nvoMlxSupTmp4
incremental
count (9)
0
Output (non-
polled)
07-Display Code
dispcode_4
30001/4
198
nvoMlxDispCode4
incremental
count (9)
0
Output (non-
polled)
11-Error Code
errcode_4
40001/4
199
nvoMlxErrCode4
51
0
Output (non-
polled)
08-Unit Status
unitstat_4
30002/4
200
nvoMlxStat4
incremental
count (9)
0
Output (non-
polled)
09-Ret Flow Temp
returntemp_4
41004/4
197
nvoMlxRetTmp4
incremental
count (9)
0
Output (non-
polled)