Section 17 bacnet data link layer options, Gateway communications manual – AERCO XPC GATEWAY Communications User Manual
Page 110

GATEWAY COMMUNICATIONS MANUAL
110
Trend_log (of a non-BACnet property):
4. Writeable
Properties:
buffer_size
client_cov_increment
cov_resubscription_inter
val
description
event_enable
log_enable
log_interval
notification_class
notification_threshold
notify_type
record_count
start_time
stop_time
stop_when_full
5. Proprietary
Properties:
None
6. Range
Restrictions:
description
log_interval
notification_class
notification_threshold
record_count
limited to 50 octets in
length
0 to 4294967295
must be valid
notification_class
0 to 4294967295
can only be written to 0
SECTION 17 BACNET DATA LINK LAYER OPTIONS
The following two prefix symbols are used in this section.
□ None of the above
* Dynamic Binding is not supported when MS/TP is configured as a slave node.
Data Link Layer Options:
XX
BACnet IP, (Annex J)
□ Able to register as a Foreign Device
XX
ISO 8802-3, Ethernet (Clause 7)
□ ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8)
XX
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8) baud rate(s) 156k baud
XX
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
□ MS/TP slave (Clause 9), baud rate(s): 9600, 19200, 38400, 76800