GATEWAY COMMUNICATIONS MANUAL

110

Trend_log (of a non-BACnet property):

4. Writeable

Properties:

buffer_size
client_cov_increment
cov_resubscription_inter
val
description
event_enable
log_enable
log_interval
notification_class
notification_threshold
notify_type
record_count
start_time
stop_time
stop_when_full

5. Proprietary

Properties:

None

6. Range

Restrictions:

description
log_interval
notification_class
notification_threshold
record_count

limited to 50 octets in
length
0 to 4294967295
must be valid
notification_class
0 to 4294967295
can only be written to 0

SECTION 17 BACNET DATA LINK LAYER OPTIONS

The following two prefix symbols are used in this section.
 None of the above
* Dynamic Binding is not supported when MS/TP is configured as a slave node.

Data Link Layer Options:

XX

BACnet IP, (Annex J)

□ Able to register as a Foreign Device

XX

 ISO 8802-3, Ethernet (Clause 7)

□ ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8)

XX

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8) baud rate(s) 156k baud

XX

MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800

□ MS/TP slave (Clause 9), baud rate(s): 9600, 19200, 38400, 76800