Gf-122 aerco xpc gateway – AERCO XPC GATEWAY Communications User Manual

Page 153

background image

GF-122 AERCO XPC GATEWAY

153

Modbus-To-N2 Protocol Mapping

1 BMS/BMS II, 12 C-More Boilers (Continued)

Equipment

Point Name

Name

Modbus Data

Addr/Unit Addr

Read

Only Enabled Type

N2

ID

Blr Addr 10

01-Fire Rate Out

boilerstate_10

30009/10

data float

91

02-Active Setpoint

effectsetpt_10

30017/10

data float

92

03-Net Remote Setpt

setpt_10

40001/10

data float

93

05-Fire Rate In

boilerload_10

30018/10

data float

95

06-Outlet Temp

localsuptemp_10

30003/10

data float

96

07-Display Code

dispcode_10

30001/10

data float

97

08-Unit Status

unitstat_10

30002/10

data float

98

09-Run Cycles

runcycles_10

30012-30013/10

data float

99

10-Run Hours

runhours_10

30014-30015/10

data float

100

Deg F or Deg C

m114_10

binary out

19

Use Temp Scaling

m101_10

binary out

20

Blr Addr 11

01-Fire Rate Out

boilerstate_11

30009/11

data float

101

02-Active Setpoint

effectsetpt_11

30017/11

data float

102

03-Net Remote Setpt

setpt_11

40001/11

data float

103

05-Fire Rate In

boilerload_11

30018/11

data float

105

06-Outlet Temp

localsuptemp_11

30003/11

data float

106

07-Display Code

dispcode_11

30001/11

data float

107

08-Unit Status

unitstat_11

30002/11

data float

108

09-Run Cycles

runcycles_11

30012-30013/11

data float

109

10-Run Hours

runhours_11

30014-30015/11

data float

110

Deg F or Deg C

m114_11

binary out

21

Use Temp Scaling

m101_11

binary out

22

Blr Addr 12

01-Fire Rate Out

boilerstate_12

30009/12

data float

111

02-Active Setpoint

effectsetpt_12

30017/12

data float

112

03-Net Remote Setpt

setpt_12

40001/12

data float

113

05-Fire Rate In

boilerload_12

30018/12

data float

115

06-Outlet Temp

localsuptemp_12

30003/12

data float

116

07-Display Code

dispcode_12

30001/12

data float

117

08-Unit Status

unitstat_12

30002/12

data float

118

09-Run Cycles

runcycles_12

30012-30013/12

data float

119

10-Run Hours

runhours_12

30014-30015/12

data float

120

Deg F or Deg C

m114_12

binary out

23

Use Temp Scaling

m101_12

binary out

24

Page 4 of 5