beautypg.com

3 configuring the bms ii, Gateway communications manual – AERCO XPC GATEWAY Communications User Manual

Page 58

background image

GATEWAY COMMUNICATIONS MANUAL

58

Net +

Net -

Shield

P

O

RT

1a

XPC GATEWAY

RS232-TO-RS485

CONVERTER

TXD

RXD

GND

GND

B (+)

A

(-)

RED (+)

BLUE (-)

GREEN (GND)

RED

ORANGE

IMPORTANT

CHECK INPUT & OUTPUT

POLARITY ON CONVERTER

BEING USED

BMS

RS232

RS485

232

ISO GND

TXD

RXD

ISO 12V

JP5

+12V

GND

Figure 3-13. Port 1a Wiring Connections for BMS

NOTE

A BMS II option is available with a built-in RS485-to-232 Converter (part no,
124943).

4. On the right side of the XPC Gateway Module, check to ensure that DIP switches 3 and 4 are set to

the ON (left) position.

3.3.1.3 Configuring the BMS II

Once the BMS II has been wired to the Gateway as described in subsection 3.3.1.1 or 3.3.1.2, turn on
power to the BMS II and perform the following configuration settings:

NOTE

Refer to AERCO Instruction Manual GF-124 for additional information on
BMS II keypad functions and displays.

1. Press the

MENU key and go to the SETUP MENU.

2. P

ress the ▲ arrow key. ENTER PASSWORD will be displayed requesting the valid password to be

entered.

3.

Using the ▲ and ▼ arrow keys, enter the valid level 1 password (159) and then press the

ENTER

key. LEVEL 1 PASSWORD will be displayed.

4. Press the

MENU key again. RS232 MENU is displayed.

5.

Press the ▲ arrow key. RS232 MODE appears in the first line of the display.

6. If MODBUS SLAVE is not displayed in the second line of the display, press the

CHANGE key and

toggle the display to MODBUS SLAVE. Press the

ENTER key to store the setting.

7. While still in the RS232 MENU

, press the ▲ arrow key. RS232 BAUDRATE is displayed in the first

line of the display.

8. If 9600 is not displayed in the second line of the display, press the

CHANGE key and select 9600

using the ▲ or ▼ arrow key. Press the

ENTER key to store the 9600 Baud Rate.