beautypg.com

4 c-more controller modbus communication interface, Gf-122 aerco xpc gateway – AERCO XPC GATEWAY Communications User Manual

Page 35

background image

GF-122 AERCO XPC GATEWAY

35

Modbus RS485 devices should be wired in a “Daisy-Chain” configuration similar to the example shown
Figure 2-1. DO NOT wire the units in a “Star” configuration where all devices are connected to a central
point (node).

BAS

MASTER

SLAVE

#1

SLAVE

#2

SLAVE

#3

SLAVE

#4

SLAVE

#5

XPC

GATEWAY

Figure 2-1. Typical Daisy-Chain Modbus/RS485 Network

Subsections 2.4 through 2.7 provide the set-up and programming instructions necessary to implement a
communications network utilizing the AERCO XPC and C-More Controller Slaves controlled by a Master
BAS.

2.4 C-MORE CONTROLLER MODBUS COMMUNICATION INTERFACE

The RS485 Modbus communication (COMM) connections for C-More Controller slaves are made in the
Input/Output (I/O) Box shown in Figure 2-2.

Identical I/O Boxes are used for Benchmark Boilers and

KC1000 Boilers or Water Heaters. The connections are made at the

RS485 COMM terminals labeled +

(plus), and

(minus). Observe the NOTE in Figure 2-2 and never terminate wire shields to the G

(Ground) terminal.