GATEWAY COMMUNICATIONS MANUAL

124

08-Num Boilers
Online

30009

Total Boilers On
Line

Input

0x0008 / 8

(0 to 40) BMS
(0 to 32) BMSII

09-Last Blr Fired

30017

Last Boiler Fired

Input

0x0010 / 16

(1 to 40) BMS
(1 to 32) BMSII

10-Boiler 1 Status

30018

Boiler 1 Status
(PWM Boiler 1)

Input

0x0011 / 17

Enum (1 to 40, 119, 120)
1 to 40 = Fired and
Sequence
119 = Not On Line
120 = On Line But Not
Fired

11-Boiler 2 Status

30019

Boiler 2 Status
(PWM Boiler 2)

Input

0x0012 / 18

Same As Above

12-Boiler 3 Status

30020

Boiler 3 Status
(PWM Boiler 3)

Input

0x0013 / 19

Same As Above

13-Boiler 4 Status

30021

Boiler 4 Status
(PWM Boiler 4)

Input

0x0014 / 20

Same As Above