GF-122 AERCO XPC GATEWAY
139
Modbus-To-BACnet Protocol Mapping
1 BMS/BMS II, 12 C-More Boilers (Continued)
Equipment
Point Name
Name
Modbus Data
Addr/Unit Addr
Read
Only Enabled
BACnet
Type:ID
Blr Addr 10
01-Fire Rate Out
boilerstate_10
30009/10
AV:130
02-Active Setpoint
effectsetpt_10
30017/10
AV:131
03-Net Remote Setpt
setpt_10
40001/10
AV:132
05-Fire Rate In
boilerload_10
30018/10
AV:124
06-Outlet Temp
localsuptemp_10
30003/10
AV:125
07-Display Code
dispcode_10
30001/10
AV:126
08-Unit Status
unitstat_10
30002/10
AV:127
09-Run Cycles
runcycles_10
30012-30013/10
AV:128
10-Run Hours
runhours_10
30014-30015/10
AV:129
Deg F or Deg C
m114_10
BV:20
Use Temp Scaling
m101_10
BV:21
Blr Addr 11
01-Fire Rate Out
boilerstate_11
30009/11
AV:140
02-Active Setpoint
effectsetpt_11
30017/11
AV:141
03-Net Remote Setpt
setpt_11
40001/11
AV:142
05-Fire Rate In
boilerload_11
30018/11
AV:134
06-Outlet Temp
localsuptemp_11
30003/11
AV:135
07-Display Code
dispcode_11
30001/11
AV:136
08-Unit Status
unitstat_11
30002/11
AV:137
09-Run Cycles
runcycles_11
30012-30013/11
AV:138
10-Run Hours
runhours_11
30014-30015/11
AV:139
Deg F or Deg C
m114_11
BV:22
Use Temp Scaling
m101_11
BV:23
Blr Addr 12
01-Fire Rate Out
boilerstate_12
30009/12
AV:150
02-Active Setpoint
effectsetpt_12
30017/12
AV:151
03-Net Remote Setpt
setpt_12
40001/12
AV:152
05-Fire Rate In
boilerload_12
30018/12
AV:144
06-Outlet Temp
localsuptemp_12
30003/12
AV:145
07-Display Code
dispcode_12
30001/12
AV:146
08-Unit Status
unitstat_12
30002/12
AV:147
09-Run Cycles
runcycles_12
30012-30013/12
AV:148
10-Run Hours
runhours_12
30014-30015/12
AV:149
Deg F or Deg C
m114_12
BV:24
Use Temp Scaling
m101_12
BV:25