Modbus-To-BACnet Protocol Mapping

1 BMS/BMS II, 12 C-More Boilers (Continued)

Equipment

Point Name

Name

Modbus Data

Addr/Unit Addr

Read

Only Enabled

BACnet

Type:ID

Blr Addr 10

01-Fire Rate Out

boilerstate_10

30009/10

AV:130

02-Active Setpoint

effectsetpt_10

30017/10

AV:131

03-Net Remote Setpt

setpt_10

40001/10

AV:132

05-Fire Rate In

boilerload_10

30018/10

AV:124

06-Outlet Temp

localsuptemp_10

30003/10

AV:125

07-Display Code

dispcode_10

30001/10

AV:126

08-Unit Status

unitstat_10

30002/10

AV:127

09-Run Cycles

runcycles_10

30012-30013/10

AV:128

10-Run Hours

runhours_10

30014-30015/10

AV:129

Deg F or Deg C

m114_10

BV:20

Use Temp Scaling

m101_10

BV:21

Blr Addr 11

01-Fire Rate Out

boilerstate_11

30009/11

AV:140

02-Active Setpoint

effectsetpt_11

30017/11

AV:141

03-Net Remote Setpt

setpt_11

40001/11

AV:142

05-Fire Rate In

boilerload_11

30018/11

AV:134

06-Outlet Temp

localsuptemp_11

30003/11

AV:135

07-Display Code

dispcode_11

30001/11

AV:136

08-Unit Status

unitstat_11

30002/11

AV:137

09-Run Cycles

runcycles_11

30012-30013/11

AV:138

10-Run Hours

runhours_11

30014-30015/11

AV:139

Deg F or Deg C

m114_11

BV:22

Use Temp Scaling

m101_11

BV:23

Blr Addr 12

01-Fire Rate Out

boilerstate_12

30009/12

AV:150

02-Active Setpoint

effectsetpt_12

30017/12

AV:151

03-Net Remote Setpt

setpt_12

40001/12

AV:152

05-Fire Rate In

boilerload_12

30018/12

AV:144

06-Outlet Temp

localsuptemp_12

30003/12

AV:145

07-Display Code

dispcode_12

30001/12

AV:146

08-Unit Status

unitstat_12

30002/12

AV:147

09-Run Cycles

runcycles_12

30012-30013/12

AV:148

10-Run Hours

runhours_12

30014-30015/12

AV:149

Deg F or Deg C

m114_12

BV:24

Use Temp Scaling

m101_12

BV:25