6-17
6-5
Setting Commands for the N-410 Series
S
6
Protocol settings
Protocol settings (only available when using PLC link)
Function
Command sent
Response
Explanation
Communication protocol
settings
* Use the next command for
handshake details
Change
WP07n
OK
n = 0: No handshake
1: PASS/RTRY
2: ACK/NAK
Confirm
RP07
07n
Header settings
Change WP51hhh...
OK
hhh... = Header (Up to 5 characters)
*Settings are specified in hexadecimal
(up to 10 characters).
*If nothing is specified, hhh... = FF
Confirm
RP51
51hhh...
Delimiter settings
Change WP52hhh...
OK
hhh... = Delimiter (Up to 5 characters)
*Settings are specified in hexadecimal
(up to 10 characters).
*If nothing is specified, hhh... = FF
Confirm
RP52
52hhh...
ID number addition
Change
WP09n
OK
n = 0: Do not add anything
1: Add
Confirm
RP09
09n
Add checksum
Change
WP39n
OK
n = 0: Do not add anything
1: Add
Confirm
RP39
39n
Function
Command sent
Response
Explanation
PLC link device
Change
WP36n
OK
n = 0: No PLC link
1: SYSMAC Series
2: MELSEC Series
3: KV Series
Confirm
RP36
36n
Trigger input via PLC link
Change
WP37n
OK
n = 0: Do not use
1: Use
Confirm
RP37
37n
DM head address
Change
WP40nn
OK
nn = 00 to 99
(0000 to 9900)
Confirm
RP40
40nn
PLC device / station number
Change
WP43nn
OK
nn = 00 to 31
Confirm
RP43
43nn