8200SHB0199
4-32
-
The motor cable should be as short as possible because of the positive
effect on the drive characteristic.
- FIG 4-19 shows the relation between the motor cable length and the
possibly required output filters.
- For group drives (several motors connected to one controller) it is
necessary to calculate the resulting cable length I
res
:
,
UHV
VXP RI DOO PRWRU FDEOH OHQJWKV ô 1R RI PRWRU FDEOHV
¯
- The components stated in FIG 4-19 are valid for chopper frequencies
$
8 kHz (C018 = -0-, -1-). When using controllers with chopper
frequencies > 8 kHz, different measures may be required. Please contact
Lenze.
- When using unscreened motor cables, the data indicated in FIG 4-19 are
valid for the double motor cable length.
- Please contact Lenze when the absolute or resulting motor cable lengths
are > 200 m.
Type
Permissible control mode C014
8201
8202
-0-, -1-,
-2-, -3-
-2-, -3-
-2-, -3-
+ motor filter/
-2-, -3-
+ sine filter
8203
-0-, -1-,
-2-, -3-
-2-, -3-
-2-, -3-
+ motor filter/
-2-, -3-
+ sine filter
8204
-2-, -3-
+ motor filter/
+ sine filter
0
15
25
50
100
200
Motor cable length (resulting), screened in m
Type
Permissible control mode C014
8211
-2-,
-3-,
-4-
-2-, -3-
-2-, -3-
-2-, -3-
8212
-2-, -3-, -4-
-2-, -3-
-2-, -3-
+ motor filter/
-2-, -3-
+ sine filter
8213/8214
+ motor filter/
motor choke
+ sine filter
8213/8214
motor choke
+ sine filter
8213/8214
8215/8216
-2-, -3-, -4-
motor choke
8215/8216
-2-, -3-, -4-
8215/8216
8217/8218
-2-, -3-, -4-
8217/8218
0
15 25
50
100
200
Motor cable length (resulting), screened in m
Type
Additionally required output filters in the motor cable
8221/8222
motor filter/motor choke
motor choke
8223/8224/8225
8226/8227
none
none
motor choke
(contact Lenze)
8241/8242/8243
8244/8245/8246
none
motor filter/motor choke
sine filter
0
50
100
200
Motor-cable length (resulting), screened in m
FIG 4-19
Output filters additionally required in the motor cable
Show/Hide Bookmarks