7-56
7.5.14.5 DC-injection brake (DCB)
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C019 Threshold auto DC
brake
821X/822X/824X
0.10
0.10
{0.02 Hz}
5.00
0.00
{0.02 Hz}
5.00 HVAC only
C035*
¤ Selection DC brake
-0-
-0-
Selection of brake voltage under
C036
-1-
Selection of brake current under
C036
HVAC only
C036 Voltage for DC brake
*
0.00
{0.02 %}
40.00
*depends on the unit
Voltage/current for
DCB
0.00
{0.02 %}
150.00 HVAC only
C106 Holding time for
autom. DC injection
brake
820X
0.00
0.00
{0.01s}
50.00
821X/822X
824X
0.02
0.00
{0.01s}
999.00
C196*
¤ Input condition
autom. DC injection
brake
-0-
-0-
DC brake active at C050 < C019
-1-
DC brake active at C050
< C019 and Setpoint < C019
HVAC only
Series “Standard”:
Function
-
DC braking enables fast deceleration of the drive to standstill without using a brake unit.
Activation
-
Via terminal
- C007 = -3-, -7-, -14-, 19:
HIGH level at terminal E2
The DC-injection brake remains active until a LOW signal is reassigned to terminal E2.
- C007 = -0-, -5-, -11-:
HIGH level at terminal E3
The DC-injection brake remains active until a LOW signal is reassigned to terminal E3.
-
Automatically
- If the field-frequency setpoint falls below the operating threshold, the DC-injection brake will be
activated for the holding time set under C106. Afterwards, the drive will set controller inhibit.
Important
The DC-motor current is directly set under code C036 (voltage for DC brake). Please observe, that
the connected motor can be overheated by overlong operation and excessive DC-motor current.
Special features
820X
Fixed operating threshold for DCB f
d
= 0.1 Hz.
821X/822X/824X
Operating threshold for DC brake adjustable under C019.
The display value of the parameter can be related to an application datum.