8200SHB0199
3-19
3.5.3
Types 822X
120 % overload
Type
8221
8222
8223
1)
8224
8225
1)
8226
8227
1)
Mains current
with mains filter/mains choke
I
mains
[A]
39.0
50.0
60.0
97.0
119
145
185
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V
$ V
DC
$ 620 V
Motor power (4 pole ASM)
at 4 kHz/8 kHz
*
P
r
[kW]
22
30
37.5
55
75
90
110
Motor power (4 pole ASM)
at 4 kHz/8 kHz
*
P
r
[hp]
30
40
50
74
100
120
148
Output power U, V, W
at 4 kHz/8 kHz
*
S
r4
[kVA]
S
r8
[kVA]
29.8
22.2
39.5
32.6
46.4
41.6
74.8
61.7
91.5
76.2
110
103.9
142
124.7
Output
current
4 kHz
*
I
r4
[A]
43
56
66
100
135
159
205
Output
current
8 kHz
*
I
r8
[A]
32
47
59
89
110
150
171
12 kHz
*
I
r12
[A]
27
40
50
62
88
120
126
16 kHz
*
I
r16
[A]
24
35
44
54
77
105
108
Noise optimised 4 kHz
*3)
I
r4
[A]
32
47
59
89
110
150
159
4)
Noise optimised 8 kHz
*3)
I
r8
[A]
29
43
47
4)
59
4)
76
4)
92
4)
100
4)
Noise optimised 12 kHz
*
I
r12
[A]
25
37
44
54
66
82
90
Noise optimised 16 kHz
*
I
r16
[A]
21
30
35
46
60
67
72
Max.
output
4 kHz
*
I
rmax4
[A]
48
70.5
89
134
165
225
270
Max.
output
current
8 kHz
*
I
rmax8
[A]
48
70.5
89
134
165
225
221
current
for
12 kHz
*
I
rmax12
[A]
40
59
75
92
114
156
164
for
60 s
2)
16 kHz
*
I
rmax16
[A]
36
53
66
81
100
136
140
60 s
2)
Noise optimised 4 kHz
*3)
I
rmax4
[A]
48
70.5
89
134
165
225
238
4)
Noise optimised 8 kHz
*3)
I
rmax8
[A]
43
64
70
4)
88
4)
114
4)
138
4)
150
4)
Noise optimised 12 kHz
*
I
rmax12
[A]
38
56
66
81
85
107
117
Noise optimised 16 kHz
*
I
rmax16
[A]
31
46
53
69
78
87
94
Power loss (operation with I
r4
)
P
loss
[W]
640
810
810
1350
1470
2100
2400
1)
Max. permissible ambient operating temperature + 35
C
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I
rx
.
3)
Only with variant “HVAC”
4)
Must only be operated with C144 = -1- (automatic chopper frequency derating at
J
max
= + 5
C). Ensure not to
exceed the currents.
*
Chopper frequency of the inverter
For more data, see chapter 3.4.4 and chapter 3.4.5.
Show/Hide Bookmarks