2 mains connection, 1 cable protection/ cable cross-section, 2 mains choke/ mains filter – Lenze 8200 Frequency inverters User Manual
Page 246: 3 controller protection, Mains connection, Cable protection/cable cross-section, Mains choke/mains filter, Controller protection, Network of several drives, 2 mains choke/mains filter

Network of several drives
8200SHB0199
10-3
10.2.2
Mains connection
10.2.2.1 Cable protection/cable cross-section
-
Mains fuses and cable cross-section of the mains cables must be selected
according to the mains current which results from the input power P
DC100
%
. Observe national standards, temperatures and other conditions.
-
Rule of thumb for the mains current in networks:
,
hv
>$@
3
98 И
ф
9
hv
-
See page 10-10.
10.2.2.2 Mains choke/mains filter
-
Use the mains chokes/mains filters assigned to the network operation.
Function:
- Mains-current limitation
- Current/power symmetry of the mains input circuits of the controllers in
decentral network operation.
-
Mains choke/mains filter must be selected according to the mains current
and the required radio interference suppression (see page 10-11).
10.2.2.3 Controller protection
Switch-on conditions
-
Ensure simultaneous mains connection of all controller connected
to the network.
Mains-failure detection at the controller when selecting decentral
supply
-
Monitoring of the mains supply of each controller:
- In the event of failure, the controllers still connected to the mains can be
overloaded.
-
Measure:
- Switch-off the whole drive network, if a mains supply fails.
-
Possibilities for detecting/indicating mains failures:
- Application of mains fuses with alarm contact.
- Application of thermal overcurrent releases (bimetall relay), which is
connected after the mains fuses.
- Application of power switches with thermal and magnetic releases as well
as integrated alarm contact to protect the cable.