2 optimising operating modes, 1 optimising motor-current control (c014 = -4-), Optimising operating modes – Lenze 8200 Frequency inverters User Manual
Page 113: Optimising motor-current control (c014 = -4-), Commissioning

Commissioning
8200SHB0199
5-8
5.4.2
Optimising operating modes
5.4.2.1
Optimising motor-current control (C014 = -4-)
820X setting range:
Function is not available
821X/822X/824X setting range:
Required codes
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C015 V/f rated frequency
50.00
7.50
{0.02 Hz}
960.00
C021 Slip compensation
0.0
0.0
{0.1 %}
20.0
C088 Rated motor current
*
0.0 ... 2.0
k rated output current
* depends on
the unit
Input only necessary
when motors not
C091 Motor cos
j
*
0.40
{0.01}
1.00
the unit
when motors not
adapted
Setting sequence
-
Drives with matching 4-pole standard motors 230/400 V in star connection must not be
connected. After having started the drive, the controller itself detects all further motor data.
-
The following drives can be optimised by entering the nameplate data ”rated motor current” and
”cos
j” under C088 or C091:
- Motor, one power class smaller than the motor assigned to the controller.
- Motor, one or two power classes smaller than the motor assigned to the controller.
- Drives with 2, 6, 8, 10 and 12 pole standard motors.
- Drives with special motors.
-
The sensorless speed control can be optimised for your application with the ”sensorless speed
control”.
1.If necessary, select
C014 = -4-.
(Factory setting)
2.Select V/f-rated frequency
(C015).
Adjustment
Calculate the frequency to be set under C015:
C015 [Hz]
400 V
V
rmotor
[V]
ô f
r
[Hz]
V
rmotor
Rated voltage to motor nameplate [V]
f
dr
Rated frequency to motor nameplate [Hz]
For standard motors with f
dr
= 50 Hz, the following settings result for C015:
Motor voltage
Motor connection
C015
230/400 V
Y
50 Hz
230/400 V
D
87 Hz
3.If necessary, parameterise
C088, C091.
These motor data must only be entered for non-matching motors.