Configuration – Lenze 8200 Frequency inverters User Manual
Page 204
Configuration
8200SHB0199
7-67
Relay output K2
Setting range 820X/821X: K2 not available.
Setting range 822X/824X:
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C117
¤ Function relay K2
-1-
-0-
Ready for operation
-1-
TRIP fault message
-2-
Motor is running
-3-
Motor is running / CW rotation
-4-
Motor is running / CCW rotation
-5-
Field frequency f
d
= 0
-6-
f
dset
reached
-7-
Q
min
reached
-8-
I
max
reached
-9-
Overtemperature (
J
max
-10
C)
-10-
TRIP or Q
min
or IMP
822X/824X
-11-
PTC warning
HVAC only
-12-
Apparent motor current
(C054) < threshold C156
-13-
Apparent motor current
(C054) < current threshold C156
and f
d
> Q
min
threshold (C017)
-14-
Apparent motor current
(C054) < threshold C156 and input
of ramp function generator = output
of ramp function generator
HVAC only
HVAC only
HVAC only
822X/824X
-15-
Warning motor phase failure
HVAC only
-16-
f
d
(C050) < f
dmin
(C010)
HVAC only
C054* Motor current
HVAC only
Display only
C156* Current threshold
0
0
{1 %}
150 HVAC only
Function
Series “HVAC”:
The changeover contact of relay K2 - terminals K21, K22, K24 - can be assigned with different
function to monitor the drive.
C008 = -12-, -13-, -14-:
-
The display value (C054) is smoothened with a ring memory with 500 ms.
-
The value set under C156 corresponds to a percentage of the rated controller current [I
r
].
-
With the control mode “Square characteristic” (C014 = 3), C156 is internally adapted via the field
frequency (C011):
C156
internal
[%]
C156 [%]ô
fd
2
[Hz
2
]
C011
2
[Hz
2
]
For instance, a belt monitoring can be implemented with this function extension.
Important
C156 is only stored in PAR1.