2 analog output, Analog output, Configuration – Lenze 8200 Frequency inverters User Manual
Page 206

Configuration
8200SHB0199
7-69
7.7.2
Analog output
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C108* Gain (C111)
128
0
{1}
255
C111
¤ Monitor signal
-0-
-0-
Field frequency
-1-
Unit load
-2-
Motor current
-3-
DC bus voltage
-4-
Motor power
-5-
Motor voltage
-6-
Analog output 1/f
d
(1/C050)
-7-
Field frequency of
f
dmin
(C010) ... f
dmax
(C011)
-8-
Actual PID controller value
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
-9-
Ready for operation
-10-
TRIP fault message
-11-
Motor is running
-12-
Motor is running / CW rotation
-13-
Motor is running / CCW rotation
-14-
Field frequency f
d
= 0
-15-
f
dset
reached
-16-
Q
min
reached
-17-
I
max
reached
-18-
Overtemperature (
Ô
max
-10
)
-19-
TRIP, Q
min
or IMP set
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
822X/824X
-20-
PTC warning
HVAC only
-21-
Apparent motor current
(C054) < current threshold (C156)
-22-
Apparent motor current
(C054) < current threshold (C156)
and f
d
> Q
min
threshold
-23-
Apparent motor current
(C054) < threshold (C156) and
input of ramp function generator =
output of ramp function generator
HVAC only
HVAC only
HVAC only
822X/824X
-24-
Warning motor phase failure
HVAC only
-25-
f
d
(C050) < f
dmin
(C010)
HVAC only
Function
Series “HVAC”:
-
To monitor the drive, you can output different process value as standardised voltage via
terminal 62.
-
With C111 = -0-, C108 = 0 ... 225 corresponds to an output voltage of 0 V ... 10 V
(at f
d
= C011).
- With C111, C108 = 128 corresponds to an output voltage of 6 V (factory setting).
-
If C111 = -6-, the analog output is reciprocal to the field frequency of the motor. This function can
for instance be used for the external display of a cycle time
- of a product or
- through a furnace.