Network of several drives
8200SHB0199
10-6
10.2.4
Fuses and cable cross-sections for a network of several
drives
The table values are valid for the operation of 821X/822X/824X controller in
DC-bus operation with PDC100 %, i.e. use of the max. rated controller power on
the DC-bus level (see page 10-10).
For operation with reduced power, it is possible to select smaller fuses and cable
cross-sections.
Type
821X/822X/824X:
Mains input L1, L2, L3, PE
DC input + V
DC
, -V
DC
, PE
Type
Operation with mains filter/mains choke
Fuse
F1, F2, F3
E.l.c.b.
Cable cross-section
1)
Fuse
F4, F5
Cable cross-section
1)
VDE
UL
VDE
mm
2
AWG
mm
2
AWG
8211 M 6A
-
B 6A
1
17
6.3A
1
17
8212 M 6A
-
B 6A
1
17
6.3A
1
17
8213 M 10A
-
B 10A
1.5
15
12A
1.5
15
8214 M 10A
-
B 10A
1.5
15
12A
1.5
15
8215 M 16A
-
B 13A
2.5
13
16A
2.5
13
8216 M 16A
-
B 16A
2.5
13
20A
4
11
8217 M 32A
-
B 32A
6
10
40A
6
10
8218 M 32A
-
B 32A
6
10
40A
6
10
8221 M 50A
50A
-
16
5
80A
16
7
8222 M 80A
80A
-
25
3
100A
25
5
8223 M 80A
80A
-
25
3
100A
25
3
8224 M 125A
125A
-
70
2/0
2x 100A
2)
2x 25 (1x 70)
2x 3 (1x 2/0)
8225 M 125A
125A
-
70
2/0
2x 100A
2)
2x 25 (1x 70)
2x 3 (1x 2/0)
8226 M 160A
175A
-
95
3/0
3x 80A
2)
3x 16 (1x 95)
3x 5 (1x 3/0)
8227 M 200A
200A
-
120
4/0
3x 100A
2)
3x 25 (1x 120) 3x 3 (1x 4/0)
8241 M 6A
5A
B 6A
1
17
6.3A
1
17
8242 M 6A
5A
B 6A
1
17
6.3A
1
17
8243 M 10A
10A
B 10A
1.5
15
12A
1.5
15
8244 M 10A
10A
B 10A
1.5
15
12A
1.5
15
8245 M 16A
20A
B 16A
2.5
13
20A
4
11
8246 M 32A
25A
B 32A
6
10
40A
6
10
1)
Observe national and regional regulations (e.g. VDE/EVU)!
2)
F4, F5 are possible because of parallel fuse connection.
Parallel connection cables can be used accordingly.