4 operating functions, 1 operating mode, Operating functions – Lenze 8200 Frequency inverters User Manual
Page 146: Operating mode, Configuration

Configuration
8200SHB0199
7-9
7.4
Operating functions
7.4.1
Operating mode
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C001
¤ Operating mode
-0-
-0-
Setpoint selection via term. 8
Control via terminals
Parameter setting via 8201BB
-1-
Setpoint selection via 8201BB or
LECOM
Control via terminals
Parameter setting via 8201BB
-2-
Setpoint selection via term. 8
Control via terminals
Parameter setting via LECOM
-3-
Setpoint selection via LECOM
Control via LECOM
Parameter setting via LECOM
Function
With the selection of the operating mode you determine the control, the setpoint selection and the
parameter setting of the drive. This setting should always be made first.
Important
When you select the setpoint via the keypad or the motor-potentiometer function, the setpoint will
be saved when switching the mains or interrupting the operation.
When changing the operating mode to ”setpoint selection via keypad” or ”setpoint selection via
LECOM”, the drive might start after enabling the controller.