C014 = -0-/-1-), Commissioning – Lenze 8200 Frequency inverters User Manual
Page 115
Commissioning
8200SHB0199
5-10
5.4.2.2
Optimise V/f-characteristic control with auto boost
(C014 = -0-/ -1-)
821X/822X/824X setting range:
Function is not available
820X setting range:
Required codes
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C015 V/f-rated frequency
50.00
30.00
{0.05 Hz}
960.00
C016 V
min
setting
*
0.00
{0.02 %}
40.00
*depends on the unit
C021 Slip compensation
0.0
0.0
{0.1 %}
12.0
Setting sequence
1.If necessary, select V/f
characteristic with auto boost
(C014 = -0- or -1-).
2.Select V/f-rated frequency
(C015).
-
The V/f-rated frequency determines the slope of the V/f characteristic and has considerable
influence on the current, torque and power performance of the motor.
-
An internal mains voltage compensation compensates deviations in the mains during operation.
Therefore, they do not have to be considered for the setting of C015.
-
Use standard motors with 230/400 V with
a connection, since with an input voltage of 230 V a
max. of 3AC 230 V is at the output.
Adjustment
Calculate the frequency to be set under C015:
C015 [Hz]
230 V
V
rmotor
[V]
ô f
dr
[Hz]
V
rmotor
Rated voltage to motor nameplate [V]
Observe the connection mode (e.g. with a
motor voltage to nameplate 230/400 V /
D
V
rmotor
= 230 V AC.
f
dr
Rated frequency to motor nameplate [Hz]
C014 = -0-
Linear characteristic
C014 = -1-
Square characteristic (e.g. for pumps, fans)
o u t
r m o t o r
V
V
1
V
m i n
0
0
1
C 0 1 5
f
d r m o t o r
o u t
r m o t o r
V
V
V
m i n
0
0
1
C 0 1 5
f
d r m o t o r
K 3 5 . 0 0 6 6 G B