2 conditions for trouble-free network operation, 1 possible combinations, Conditions for trouble-free network operation – Lenze 8200 Frequency inverters User Manual
Page 245: Possible combinations, Network of several drives, Stop

Network of several drives
8200SHB0199
10-2
10.2
Conditions for trouble-free network operation
Stop!
-
The installation and assembly notes must be applied (chapter 4).
-
Connect controllers only when they have similar DC-bus/mains-voltage
ranges (see the following table).
-
Adapt the thresholds of brake units and input and feedback modules.
-
All supplies should only be operated with the prescribed mains
chokes/mains filters! (See page 10-11)
10.2.1
Possible combinations
Possible combinations of Lenze controllers in DC-bus connection:
Type
Data
820X
821X
822X
824X
93XX
820X
**)
➀
1 / N / PE / AC / 190 ... 260 V
á0 %/ 50 Hz/60 Hz
➁
270 V ... 360 V
➂
375 V
821X
➀
3 / PE / AC / 320 ... 510 V
á0 %/ 50 Hz/60 Hz
➁
450 V ... 715 V
➂
725 V
*)
822X
➀
3 / PE / AC / 320 ... 528 V
á0 %/ 50 Hz/60 Hz
➁
460 V ... 740 V
➂
725/765 V
*)
824X
➀
3 / PE / AC / 320 ... 528 V
á0 %/ 50 Hz/60 Hz
➁
460 V ... 740 V
➂
725/765 V
*)
93XX
➀
3 / PE / AC / 320 ... 528 V
á0 %/ 50 Hz/60 Hz
➁
460 V ... 740 V
➂
725/765 V
*)
➀
Max. permissible mains-voltage range
➁
DC-bus voltage range
➂
Operating threshold - brake unit
*)
Set the thresholds of all units connected to the DC-bus to the same value.
Procedure: See the corresponding Operating Instructions.
**)
Central supply only possible from a DC source