Technical data – Lenze 8200 Frequency inverters User Manual
Page 39

Technical Data
8200SHB0199
3-7
150 % overload
8214
8213
8212
8211
Type
EVF8214-E
EVF8213-E
EVF8212-E
EVF8211-E
Order No.
8214-V020
8213-V020
8212-V020
8211-V020
Type
Variant “HVAC”
EVF8214-E-V020
EVF8213-E-V020
EVF8212-E-V020
EVF8211-E-V020
Order No.
Motor voltage
3)
V
M
[V]
0 - 3 x V
mains
/ 0 Hz
¡ 50 Hz, if required up to 480 Hz
Power loss (operation with I
rx
)
P
loss
[W]
55
75
90
100
Power derating
[%/K]
[%/m]
40
C < T
V
< 50
C: 2.5 %/K
1000 m a.m.s.l.
h $ 4000 m a.m.s.l.: 5 %/1000 m
Field
frequency
Resolution
Absolute
0.02 Hz
Field
frequency Digital setpoint selection
Accuracy
á0.05 Hz
Analog setpoint selection
Linearity
á0.5 %(max. selected signal level: 5 V or 10 V)
Analog setpoint selection
Temperature
sensitivity
0
¡ 40 C: +0.4 %
Offset
á0 %
Weight
m [kg]
2.2
2.2
2.2
2.2
Printed in bold
Data for the operation with factory setting and a chopper frequency of 8 kHz.
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I
rx
.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
4)
Only with variant “HVAC”
*
Chopper frequency of the inverter
Show/Hide Bookmarks