Technical data – Lenze 8200 Frequency inverters User Manual
Page 41

Technical Data
8200SHB0199
3-9
150 % overload
Type
8215
8216
8217
8218
Order No.
EVF8215-E
EVF8216-E
EVF8217-E
EVF8218-E
Variant ”Cold Plate”
Type
8215-V003
8216-V003
8217-V003
8218-V003
Variant ”Cold Plate”
Order No.
EVF8215-C-V003 EVF8216-C-V003 EVF8217-C-V003 EVF8218-C-V003
Variant “HVAC”
Type
8215-V020
8216-V020
8217-V020
8218-V020
Order No.
EVF8215-E-V020 EVF8216-E-V020 EVF8217-E-V020 EVF8218-E-V020
Motor voltage
3)
V
M
[V]
0 - 3 x V
mains
/ 0 Hz
¡ 50 Hz, if required up to 480 Hz
Power loss (operation with I
rx
)
P
loss
[W]
150
200
280
400
Power derating
[%/K]
[%/m]
40
C < T
V
< 50
C: 2.5 %/K
1000 m a.m.s.l.
h $ 4000 m a.m.s.l.: 5 %/1000 m
Field
frequency
Resolution
Absolute
0.02 Hz
Field
frequency Digital setpoint selection
Accuracy
á0.05 Hz
Analog setpoint selection
Linearity
á0.5 %(max. selected signal level: 5 V or 10 V)
Analog setpoint selection
Temperature
sensitivity
0
¡ 40 C: +0.4 %
Offset
á0 %
Weight
”Cold Plate” without heat sink
”Cold Plate” with heat sink
m [kg]
5.3
2.8
20.8
5.3
2.8
20.8
5.3
2.8
20.8
5.3
2.8
20.8
Printed in bold
Data for the operation with factory setting and a chopper frequency of 8 kHz.
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I
rx
.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
4)
Only with variant “HVAC”
*
Chopper frequency of the inverter