5 decentral supply, 1 decentral supply for 820x, Decentral supply – Lenze 8200 Frequency inverters User Manual
Page 259: Decentral supply for 820x, Network of several drives, Stop
Network of several drives
8200SHB0199
10-16
10.5
Decentral supply
The DC-bus is supplied via several controllers or supply units connected in parallel
to the mains.
10.5.1
Decentral supply for 820X
820X
U V W
PE
L1
N -UG +UG
820X
U V W
PE
L1
N -UG +UG
Z3
F1 F1*
F1 F1*
Z1 Z1*
Z1 Z1*
F4 F5
F4 F5
-UG +UG
K10
PE
L1
PE
N/L2
K10*
FIG 10-4
Block diagram: Decentral supply of several 820X controllers connected to a network
F1, F1*
Fuses, see Accessories
F1*only for supply voltage 2AC / PE / 190 - 260 V
0 %/ 45 - 65 Hz 0 %
K10, K10*
Mains contactor
K10*only for supply voltage 2AC / PE / 190 - 260 V
0 %/ 45 - 65 Hz 0 %
F4, F5
Fuses, DC level, see Accessories
Z1, Z1*
Mains choke/mains filter, see Accessories
Z1*only for supply voltage 2AC / PE / 190 - 260 V
0 %/ 45 - 65 Hz 0 %
Z3
Brake chopper/brake module, see Accessories
Stop!
For faultless network operation, the following conditions must be fulfilled in addition
to the conditions described in chapter 10.2:
-
In-phase connection on the mains side
-
With two-phase supply
- Cable and overload protection via second assigned mains fuse F1*
- Ensure current and power symmetry by providing a second mains
choke/mains filter Z1*.