3 setpoint input via jog frequencies, Setpoint input via jog frequencies, Configuration – Lenze 8200 Frequency inverters User Manual
Page 180

Configuration
8200SHB0199
7-43
7.5.11.3 Setpoint input via JOG frequencies
Code
Name
Possible settings
IMPORTANT
Lenze Choice
Info
C037 JOG value 1
20.00 0.00
{0.02 Hz}
480.00
-480.00
{0.02 Hz}
480.00 HVAC only
C038 JOG value 2
30.00 0.00
{0.02 Hz}
480.00
-480.00
{0.02 Hz}
480.00 HVAC only
C039 JOG value 3
40.00 0.00
{0.02 Hz}
480.00
-480.00
{0.02 Hz}
480.00 HVAC only
Function
The setpoint input via JOG frequencies is only active, if C007 is set accordingly
(series “Standard”: see chapter 7.8, “Code table”; series “HVAC”: see chapter 7.9, ”Code table”).
Activate
-
JOG value 1 via control terminal E1 or
-
binary coded up to three JOG frequencies via the control terminals E1 and E2.
Activation
Series “Standard”:
-
C007 = -3-, -4-, -5-, -6-, -9-, -14-, -15-, -20-, -22-:
Function
E1
Other setpoint source
LOW
JOG 1 active
HIGH
-
C007 = -0-, -1-, -2-, -16-:
Function
E1
E2
Other setpoint source
LOW
LOW
JOG 1 active
HIGH
LOW
JOG 2 active
LOW
HIGH
JOG 3 active
HIGH
HIGH
Series “HVAC”:
-
C007 = -0-,
…
-6-, -9-, -14-, -15-, -16-, -20-, -22-, -28-, -29-,
-30-, -35-, -37-
…
-41-, -46-, -47-, -49-, -50:
Function
EX
Other setpoint source
LOW
JOG 1 active
HIGH
or
Function
E1 (E3)
E2 (E4)
Other setpoint source
LOW
LOW
JOG 1 active
HIGH
LOW
JOG 2 active
LOW
HIGH
JOG 3 active
HIGH
HIGH
Important
-
The setting of f
dmax
(C011) limits the field frequency also for JOG values.
-
The setting of f
dmin
(C010) is not effective for setpoint input by means of JOG values.
Special features
The display value of the parameter can be related to an application datum (C500, C501)
(see chapter 7.6.3).