Configuration
8200SHB0199
7-26
7.5.7
Configuration
Only “HVAC” controllers
Code
Name
Possible settings
IMPORTANT
Code
Name
Lenze
Choice
Info
IMPORTANT
C005
¤ Configuration
-0-
-0-
Operation with open-loop control via
terminal 8
-1-
Operation with open-loop control via
terminal 8 with setpoint summation
via frequency input E1
-2-
Operation with open-loop control via
frequency input E1 with setpoint
summation via terminal 8
If C005 = -0-
-
2 ms cycle time
If C005 = -1- ... -7-
-
4 ms cycle time
-3-
Open-loop operation via frequency
input E1 with apparent current
limitation via terminal 8
C005 = -3-
possible with
C014 = -2-, -4-
-6-
Operation with closed-loop control;
setpoint via terminal 8 with digital
frequency feedback via terminal E1
-7-
Closed-loop operation; setpoint via
frequency input E1 with analog
feedback via terminal 8
Function
The signal flow in the controller can be changed under C005. The functionality of the controller will
be changed when changing C005. The signal-flow charts in chapter 16.3 show the structure for
each configuration.
Special features
The selection C005 = -4-, -5- cannot be used.