3 general data/ application conditions, General data/application conditions, Technical data – Lenze 8200 Frequency inverters User Manual
Page 36: 3 general data/application conditions

Technical Data
8200SHB0199
3-4
3.3
General data/application conditions
Field
Values
Vibration resistance
Germanischer Lloyd, general conditions
Humidity class
Humidity class F without condensation (average relative humidity 85 %)
Permissible temperature
range
During transport of the controller:
-25
C¡+70 C
Permissible temperature
range
During storage of the controller:
-25
C¡+55 C
During operation of the controller:
0
C¡+40 C
+ 40
C¡+50 C
without power derating
with power derating
Permissible installation
height
h
$ 1000 m a.m.s.l.
1000 m a.m.s.l.
h $ 4000 m a.m.s.l.
without power derating
with power derating
Degree of pollution
VDE 0110 part 2 pollution degree 2
Noise emission
Requirements to EN 50081-2, EN 50082-1, IEC 22G-WG4 (Cv) 21
Limit value class A to EN 55011 (industry) with mains filter
Limit value class B to EN 55022 (residential area) with mains filter and installation into control
cabinet
Noise immunity
Limit values maintained with mains filter
Requirements to EN 50082-2, IEC 22G-WG4 (Cv) 21
Requirements
Standard
Severities
ESD
EN61000-4-2
3, i.e. 8 kV with air discharge,
6 kV with contact discharge
RF interference (enclosure)
EN61000-4-3
3, i.e. 10 V/m; 27
¡1000 MHz
Burst
EN61000-4-4
3/4, i.e. 2 kV/5 kHz
Surge
(Surge on mains cable)
IEC 1000-4-5
3, i.e. 1.2/50
³s,
1 kV phase-phase,
2 kV phase-PE
Insulation strength
Overvoltage category III to VDE 0110
Packaging to DIN 4180
Types 820X, 821X, 824X
Types 822X,
821X/2X/4X HVAC (V020)
Dust packaging
Transport packaging
Enclosure
Types 82XX, 82XX HVAC (V020)
IP20
NEMA 1: Protection against contact
Types 8215 - 8218, 822X, 824X,
8215/16/17/18/2X/4X HVAC (V020)
IP41 on the heat-sink side with thermal separation in
push-through technique
Approvals
Types 82XX, 82XX HVAC (V020)
CE:
Low-Voltage Directive and
Electromagnetic Compatibility
Types 822X, 824X,
822X/4X HVAC (V020)
UL 508:
UL 508C:
Industrial Control Equipment
Power Conversion Equipment
Show/Hide Bookmarks